Point Programming For 5496; Point Programming For Ecs-Amp's - Honeywell Farenhyt IFP-2000 Manual

Analog/ addressable fire system, emergency communication system
Table of Contents
Model IFP-2000/ECS Installation Manual
9.5.4

Point Programming for 5496

To program module points:
1.
Enter the installer code. The panel will automatically go to the main menu.
2.
Select 7 for Panel Programming.
3.
Press 4 to enter point menu.
4.
Press the Up or Down arrow to select the desired module. Refer to Section 8.6 for available choices, then
press ENTER.
Select a name
for the Point
Figure 9-7 Programming Points Screen for the 5880 Module
5.
Enter the point number, then press ENTER.
6.
Press the Up or Down arrow to select the type (See Figure 9-5 on page 19). Then press ENTER.
7.
Press ENTER to edit point name. See Appendix B. Or Press the right arrow to skip point name edit.
8.
Repeat Steps 1 through 7 for all points.
9.5.5

Point Programming for ECS-AMP's

To program module points:
1.
Enter the installer code. The panel will automatically go to the main menu.
2.
Select 7 for Panel Programming.
3.
Press 4 to enter point menu.
4.
Press the Up or Down arrows to select the desired module. Refer to Section 8.6 for available choices. Then
press ENTER.
Enter Point
Select a name
for the Point
Figure 9-8 Programming Points Screen for the ECS-AMP Module
5.
Enter the point number, then press ENTER. Points 5-8 on ECS-50W or ECS-125W will not be available
unless the ECS-CE4 is installed.
6.
Press the Up or Down arrows to select the type (notification or unused), then press ENTER.
7.
Press ENTER to edit point name. See Appendix B. Or Press the right arrow to skip point name edit.
9-17
Enter Point
Select AUX DOOR, CONSTANT
or AUX RESET
Select NOTIF or Unused
151430-L8