8.4 Faults

8.4
Faults
Faults
Faults have the following properties:
● The fault causes the motor to be switched off.
● Faults must be acknowledged.
● Faults are displayed as follows:
– In the PLC according to the PROFIdrive message class
– On the drive via LEDs
– At the drive using the three-digit display according to the PROFIdrive message class
– In the Web server via the "Diagnostics - Messages" view
Acknowledge fault
Before you can acknowledge a fault, you must have resolved the cause of the fault.
To acknowledge, you have the following options:
● Acknowledging via the PLC
● Acknowledging via the OK button under the front cover
● Switch off the converter power supply and switch on again
● Acknowledging via the Web server
● The Safety Integrated error is acknowledged by selecting/deselecting the STO function.
Any active messages of additional Safety Integrated Functions are acknowledged
simultaneously with extended message acknowledgment (p9507.0 = 1). In addition, you
must execute the standard acknowledgment mechanism.
Faults detected during the converter-internal monitoring of hardware and firmware can be
acknowledged only by switching the power supply off and on again. In the list of faults, you will
find the information on limitations when acknowledging at the corresponding fault codes.
Reference
You can find additional information on faults in Chapter "Overview of faults and alarms
(Page 419)".