Siemens SINAMICS S210 Operating Instructions Manual page 215

Servo drive system, converter, servomotor
Hide thumbs Also See for SINAMICS S210:
Table of Contents
Basic information on commissioning Safety in the web server
● Safety settings can only be made in the "Safety Integrated commissioning" mode. The drive
is in a safe state (STO active) as long as the commissioning mode is active.
The commissioning mode is activated in step "Function selection" using the "Start" button.
● You must completely run through the Safety commissioning. It is not possible to cancel
commissioning.
● A password can be defined to protect against unauthorized changes to Safety settings. This
can either be done at the beginning or at the end of the Safety commissioning.
The drive issues an alarm if a password has not been defined.
● You can find faults and alarms for Safety Integrated in the general message window.
It is not possible to access faults and alarms after you have started to commission Safety
Integrated. In the web server you only see alarms such as A01698 as "gone".
● You can check the Safety settings that have been set in the read mode at a later point in
time. This function is available to you – both as administrator or if you are logged into
SINAMICS.
Displaying the Safety commissioning view
The individual commissioning steps are displayed in the header of the "Safety Commissioning"
screen form.
SINAMICS S210 servo drive system
Operating Instructions, 01/2019, A5E41702836B AC
Commissioning and diagnostics using the web server
6.3 Commissioning Safety Integrated
213