Honeywell AlarmNet 7845i-GSM Installation And Setup Manual page 28

Internet communication
Hide thumbs Also See for AlarmNet 7845i-GSM:
Table of Contents
Internet Communication Module 7845i-GSM Installation and Setup Guide
PROMPTS
Notify Panel Of_
22
(Neither Fault)_
Flt Rel ON Y/N
23
(N)_
Pwr Loss Rpt Y/N
24
(Y)_
Low Bat Rpt Y/N
25
(Y)_
Tamper Rpt Y/N
26
(Y)_
Lynx Panic Y/N
27
(N)_
If desired, 4204 mode supports two optional hardwire zone input triggers by making connections to the module's zone
6 and/or zone 7 terminals and programming the appropriate zone trigger options below.
NOTE: These triggers are not available when using 2-4204 mode.
Zone Trigger Mode provides six hardwire zone input triggers by making connections to the module's zone terminals
and programming the appropriate zone trigger options below. Zones are numbered 1-7, with zone 2 serving as a
reporting zone only (see Bell Output Zone below).
Bell Output Zone 1 (and 2): The zone 1 terminal can detect both pulsed and steady signals. If connecting the bell
output to the 7845i-GSM zone causes a bell fault on the control panel, enable the "Trip Inputs 1or2" option. The
7845i-GSM reports an alarm on zone 1 (fire) when it detects a pulsed signal and an alarm on zone 2 (burglary) when it
detects a steady signal.
Telco Zone and Open/Close Zone: Dedicated zones can be assigned as the telco fault zone and/or an open/close
(arm/disarm) reporting zone. When triggered, these zones report a telco line fault or open/close report respectively, in
ADEMCO High-Speed format. Connect the appropriate trigger from the control to the selected zone input for each of
these options.
Input Trigger Types: Triggering of each zone input can be programmed to cause an alarm under one of the following
conditions:
• (V+), where a positive voltage causes an alarm for normally low connections
3-12
4204/
ZONE
ENTRY
2-4204
TRIG.
Important Information Regarding Zone Input Options
OPTIONS
If "Both IP and GSM Fault" is selected, the device
[Neither
will only notify the control panel if both
fault]
communication paths fail, but will always send
[Both IP
notification of either failure to the central station.
and GSM
NOTE: The fault relay output (if programmed) will
Faults]
be triggered only if "Both IP and GSM Faults" is
selected.
Press the [space] key to scroll through choices.
If enabled, the fault open collector output is
[Y], [N]
normally energized to ground, and de-energizes
(open circuit) in the event of a module radio fault.
Use if fail-safe mode is desired.
See Wiring for Module Radio Faults in Section 2.
UL NOTE: Must be set to "Y".
Sends a primary power loss report to the central
[Y], [N]
station within 1-3 hours after its detection. A
restore report is sent within 1-3 hours after power
is restored.
[Y], [N]
Sends a low-battery report when a low battery
condition exists. A low-battery restore is
automatically sent when the low battery condition
clears.
NOTE: Must be set to "N" for use with LynxR-I
controls.
Sends a tamper report when the module detects a
[Y], [N]
tamper condition. A tamper restore is
automatically sent when the tamper condition
clears.
[Y], [N]
Applies only if used with a Lynx, LynxR or
LynxR-EN control LRR trigger connected to the
module's zone terminal.
Reports a Panic alarm on zone 3 when the module
detects a single pulse on zone 1.
No restores are generated for a Panic alarm.
DESCRIPTION
Table of Contents
loading

Table of Contents