Power Connections And Options - Honeywell AlarmNet 7845i-GSM Installation And Setup Manual

Internet communication
Hide thumbs Also See for AlarmNet 7845i-GSM:
Table of Contents

Power Connections and Options

Primary power for the 7845i-GSM is provided by the AC plug-in transformer. For ECP
communication, you must also connect the +12VDC AUX voltage output of the control panel
(9.6V-13.8V typical) (see Figure 9). In the case of the LynxR-I, primary power is supplied by
the LynxR-I unit through the LRR/IP communication port.
In all installations, TB1-4 GND must be connected to ground (GND) on the control panel.
NOTE: When calculating the total load on the auxiliary power output of the control panel,
12V AUX
GND
CONTROL PANEL
Figure 9. Powering the 7845i-GSM
budget 10mA for the 7845i-GSM when using ECP mode.
TRANSFORMER
MODEL No. 1332
BATTERY
ADEMCO
K14139
Section 2: Mounting and Wiring
TB1
AC INPUT 1
1
AC INPUT 2
2
ECP (+) VOLTAGE
3
GND
4
5
Z1/ Z2 or DATA IN
11
RAD FLT
J1
7845i-GSM
2-7
Table of Contents
loading

Table of Contents