Wiring For Module Radio Faults - Honeywell AlarmNet 7845i-GSM Installation And Setup Manual

Internet communication
Hide thumbs Also See for AlarmNet 7845i-GSM:
Table of Contents
Internet Communication Module 7845i-GSM Installation and Setup Guide
Figure 5. Wiring the 7845i-GSM Zone 1 Input for a Ground (-) Triggered Bell Output

Wiring for Module Radio Faults

You may wire and program the module's fault output trigger for fail-safe mode (see the
question "FLT REL ON Y/N").
To sense a module fault at the control panel, make connections as shown in Figure 7,
including the proper EOL resistor required by the control.
2-4
+12 V AUX
GND
BELL (+)
BELL ( )
CONTROL PANEL
TRANSFORMER
MODEL No. 1332
9
LRR / AAV
TRIGGER
8
LYNXR/LYNXR-EN
CONTROL PANEL
Figure 6. Wiring the 7845i-GSM Zone 1 Input to a LynxR Trigger Output
TRANSFORMER
MODEL No. 1332
(+)
( )
BATTERY
ADEMCO
TB1
AC INPUT 1
1
AC INPUT 2
2
GND
4
2K EOL
RESISTOR
ZONE INPUT Z1/Z2
5
BATTERY
ADEMCO
K14139
TB1
AC INPUT 1
1
AC INPUT 2
2
ECP (+) VOLTAGE INPUT
3
GND
4
5
ZONE INPUT Z1/Z2
J1
7845i-GSM
K14139
7845i-GSM-006-V0
J1
7845i-GSM
7845i-GSM-019-V0