Honeywell AlarmNet 7845i-GSM Installation And Setup Manual page 22

Internet communication
Hide thumbs Also See for AlarmNet 7845i-GSM:
Table of Contents
Internet Communication Module 7845i-GSM Installation and Setup Guide
ECP mode supports two optional hardwire zone input triggers by making connections to the module's zone 6 and/or
zone 7 terminals and programming the appropriate zone trigger options below.
Each zone input can be programmed to cause an alarm under one of the following conditions:
• (EOLR) End of Line Resistor, where the input is supervised by an appropriate EOL resistor. The zone can be
triggered by NO or NC contacts, or open collector ground, or voltage trigger outputs
• (V+), where a positive voltage causes an alarm for normally low connections
• (V–), where a ground trigger causes an alarm for normally high connections
In addition to the above, zones can be programmed for an Inverted Trigger, where the alarm and normal states of
the zones are inverted; this can serve a fail-safe supervisory purpose for certain installations.
These zone inputs can also be programmed for restore reporting, and for delayed reporting, which allows time for
the user to abort false alarms.
NOTE: Optional hardwire zones report in ADEMCO High-Speed format.
PROMPTS
Enable Zn6 Y/N
31
(N)_
Zn6 Trigger Type
32
(V+)_
Invert Zn6 Y/N
33
(N)_
Restore Zn6 Y/N
34
(Y)_
Delay Zn6 (secs)
35
(00)_
Enable Zn7 Y/N
36
(N)_
Zn7 Trigger Type
37
(V)_
Invert Zn7 Y/N
38
(N)_
Restore Zn7 Y/N
39
(Y)_
Delay Zn7 (secs)
40
(00)_
Use DHCP Y/N
41
(Y)_
NIC IP Address:
42
255.255.255.255_
Subnet Mask:
43
255.255.255.255_
3-6
Important Information Regarding Zone Input Options
ENTRY
OPTIONS
[Y], [N]
• (V+)
• (V–)
• (EOLR)
[Y], [N]
[Y], [N]
[01-15]
[00] = no delay
[Y], [N]
• (V+)
• (V–)
• (EOLR)
[Y], [N]
[Y], [N]
[01-15]
[00] = no delay
[Y], [N]
12 digit:
xxx.xxx.xxx.xxx
12 digit:
xxx.xxx.xxx.xxx
DESCRIPTION
Enables alarm reporting for zone 6.
If [N], skip to Prompt 36: "Enable Zn7."
Selects the triggering method for this zone input.
Press the [space] key to scroll through choices.
Inverts the alarm and normal states of the zone 6
trigger; otherwise uses normal input signal.
Enables restore reporting for zone 6.
Defines the reporting delay in seconds for zone 6.
Enables alarm reporting for zone 7.
If [N], skip to Prompt 41: "Use DHCP."
Selects the triggering method for this zone input.
Press the [space] key to scroll choices.
Inverts the alarm and normal states of the zone 7
trigger; otherwise, uses normal input signal.
Enables restore reporting for zone 7.
Defines the reporting delay in seconds for zone 7.
Dynamically allocates the IP addresses (recommended);
then skip to Prompt 46: "Review?"
If [N], uses fixed IP addresses.
Enter the 4-part address for this device. The 4 parts of
the address must be separated by spaces (displayed as
periods in Review mode).
Enter the 32-bit address mask used to indicate the
portion (bits) of the IP address that is being used for
the subnet address. The 4 parts of the address must be
separated by spaces (displayed as periods in Review
mode).