Oil Change Warning / Error Function - Bosch rexroth Sytronix FcP 5020 Quick Start Manual

Frequency-controlled pump drive system
Hide thumbs Also See for rexroth Sytronix FcP 5020:
Table of Contents
FcP 5020
Fig. 7-22: F4.16 maximum pump pressure failure
Actual pressure monitoring function works all the time, no matter
when drive is in operation or standby.

7.10.4 Oil Change Warning / Error Function

Code
Name
Protection function config-
F4.00
uration word
Warning
hours
F4.51
change
F4.52 Error hours of oil change
F4.53 Oil in operation time
F4.54 Reset oil in operation time 0...1
Tab. 7-22: Parameter list of oil change warning / error function
Oil change monitoring function can be activated by Bit3 of F4.00.
Oil operation time will be counted and saved in F4.53 when frequency converter
starts running. If this time exceeds warning or error level in [F4.51] or [F4.52],
warning or error signal will be generated. Parameter F4.54 = 1 is used to reset
the oil operation timer F4.53.
Time counter is only active during drive in operation.
DOK-RCON03-FCP5020****-QU04-EN-P
Setting range
0...15
Bit0: Pressure sensor failure (PSF)
Bit1: Actual pressure monitoring
Bit2: p/Q max. command limit
Bit3: Oil changing detection
of
oil
0...60,000 hours
0...60,000 hours
0...60,000 hours
Bosch Rexroth AG
Block Diagram of Main Functions
Default
0
36,000
40,000
0
0
Min.
Attri.
-
Run
1
Run
1
Run
-
Read
-
Run
49/83