Analog Input - Bosch rexroth Sytronix FcP 5020 Quick Start Manual

Frequency-controlled pump drive system
Hide thumbs Also See for rexroth Sytronix FcP 5020:
Table of Contents
FcP 5020

6.2 Analog Input

This section shows how analog input can be configured. The following figure is
an example for analog input AI2, which has been assigned to pressure feedback.
The configuration for AI1, EAI and EAI2 is similar to AI2, only with different pa-
rameters shown in the table below.
Fig. 6-2: Example with analog input AI2 assigned to pressure feedback
Code
Name
E1.35 AI1 input mode
E1.40 AI2 input mode
H8.05 EAI input mode
H8.30 EAI2 input mode
DOK-RCON03-FCP5020****-QU04-EN-P
Setting Range
0: 0...20 mA
1: 4...20 mA
2: 0...10 V
3: 0...5 V
4: 2...10 V
0...4 (same as E1.35)
5: -10V...10V
0: 0...20 mA
1: 4...20 mA
2: 0...10 V
3: 0...5 V
4: 2...10 V
5: -10...10 V
Bosch Rexroth AG
Electric Connection
Default
Min.
Attri.
2
-
Run
1
-
Run
0
-
Stop
0
-
Stop
11/83