Mitsubishi Electric FR-E700 Instruction Manual page 420

Hide thumbs Also See for FR-E700:
Table of Contents
Communication operation and setting
Communication specifications
Item
Communication protocol
Conforming standard
Number of inverters connected
Communication speed
Control protocol
Communication method
Communication
specifications
Waiting time setting
Tab. 6-87: Communication specifications
6 - 266
Description
Modbus®-RTU protocol
EIA-485 (RS-485)
1 : N (maximum 32 units), setting is 0 to 247 stations
Can be selected from 4800/9600/19200 and 38400 bps
Asynchronous system
Half-duplex system
Character system
Binary (fixed to 8 bits)
Start bit
1bit
Stop bit length
Select from the following three types
No parity, stop bit length: 2 bits
Odd parity, stop bit length: 1 bit
Parity check
Even parity, stop bit length: 1 bit
Error check
CRC code check
Terminator
Parameter
Related
Parameters
Pr. 549
Pr. 117
Pr. 118
Pr. 120

Hide quick links:

Table of Contents
loading

This manual is also suitable for:

Fr-e720s sc ecFr-e720s sc eneFr-e740 sc ecFr-e740 sc ene

Table of Contents