Communication operation and setting
Operation mode switching and communication startup mode (Pr. 79, Pr. 340) (FR-E700 SC ENE)
Check the following before switching the operation mode.
– The inverter is at a stop.
– Both the STF and STR signals are off.
– The Pr. 79 Operation mode selection setting is correct. (Check the setting on the operation
panel of the inverter (refer to page 6-206).)
● The operation mode at power ON and at restoration from instantaneous power failure can be
selected. Set a value other than "0" in Pr. 340 Communication startup mode selection to select the
Network operation mode (refer to page 6-218).
● After the inverter starts up in the Network operation mode, parameter write can be commanded
via the network.
NOTES
The changed value in Pr. 340 is applied after the next power-ON or inverter reset.
The Pr. 340 setting can be changed on the operation panel in any operation mode.
When setting a value other than "0" in Pr. 340, make sure that the communication settings of the
inverter are correct.
6 - 244