Parameter
Forward/reverse signal
NOTES
When Pr. 250 is set to any of "0 to 100, 1000 to 1100", the motor coasts to a stop if the start com-
mand is turned off. (Refer to section 6.9.3.)
The STF and STR signals are assigned to the STF and STR terminals in the initial setting. The STF sig-
nal can be assigned to Pr. 178 "STF terminal function selection" and the STR signal to Pr. 179 "STR
terminal function selection" only.
FR-E700 SC EC/ENE
Inverter
Start signal
ON
ON
Function assignment of external terminals
Fig. 6-56:
2-wire type connection (Pr. 250 = 8888)
Time
I001149E
6 - 123