Parameter
6.7

Acceleration and deceleration

Purpose
Motor acceleration/deceleration time
setting
Starting frequency
Set acceleration/deceleration
pattern suitable for application
Automatically set optimum
acceleration/deceleration time
6.7.1

Acceleration and deceleration time

(Pr. 7, Pr. 8, Pr. 20, Pr. 21, Pr. 44, Pr. 45, Pr. 147)
Used to set motor acceleration/deceleration time. Set a larger value for a slower speed increase/de-
crease or a smaller value for a faster speed increase/decrease.
Pr. No. Name
FR-E720S-110SC or less,
FR-E740-095SC or less
7
Acceleration time
FR-E740-120SC and 170SC
FR-E740-230SC and 300SC
FR-E720S-110SC or less,
FR-E740-095SC or less
8
Deceleration time
FR-E740-120SC and 170SC
FR-E740-230SC and 300SC
Acceleration/
deceleration
20
reference
frequency
Acceleration/
21
deceleration time
increments
FR-E720S-110SC or less,
Second
FR-E740-095SC or less
acceleration/
44
FR-E740-120SC and 170SC
deceleration time
FR-E740-230SC and 300SC
Second
45
deceleration time
Acceleration/
deceleration time
147
switching
frequency
The above parameters can be set when Pr. 160 "User group read selection" = 0.
Depends on the Pr. 21 "Acceleration/deceleration time increments" setting. The initial value for
the setting range is "0 to 3600 s" and the setting increments is "0.1 s".
FR-E700 SC EC/ENE
Parameters that must be set
Acceleration/deceleration times
Starting frequency and start-time hold
Acceleration/deceleration pattern
Automatic acceleration/deceleration
Setting
Initial Value
Range
5 s
0–3600 s/
10 s
0–360 s
15 s
5 s
0–3600 s/
10 s
0–360 s
15 s
50 Hz
1–400 Hz
0
0
1
5 s
0–3600 s/
10 s
0–360 s
15 s
0–3600 s/
0–360 s
9999
9999
0–400 Hz
9999
9999
Description
Set the motor acceleration time.
Set the motor deceleration time.
Set the frequency that will be the basis
of acceleration/deceleration time.
As acceleration/deceleration time, set
the frequency change time from stop to
Pr. 20.
Increments:
0.1 s
Increments and
Range:
setting range of
0–3600 s
acceleration/
deceleration time
Increments:
setting can be
0.01 s
changed.
Range:
0–360 s
Set the acceleration/deceleration time
when the RT signal is on.
Set the deceleration time when the RT
signal is on.
Acceleration time = deceleration time
Frequency when automatically
switching to the acceleration/
deceleration time of Pr. 44 and Pr. 45.
No function
Acceleration and deceleration
Refer to
Section
Pr. 7, Pr. 8, Pr. 20,
6.7.1
Pr. 21, Pr. 44,
Pr. 45, Pr. 147
Pr. 13, Pr. 571
6.7.2
Pr. 29
6.7.3
Pr. 61–Pr. 63,
6.7.4
Pr. 292
Parameters referred to
3
Base frequency
29
Acceleration/deceleration
pattern selection
125
Frequency setting gain
frequency
126
Frequency setting gain
frequency
178–184
Input terminal function
selection
Refer to
Section
6.5.1
6.7.3
6.16.3
6.16.3
6.10.1
6 - 71