Parameter overview
Parameter
Func-
Name
tion
72
PWM frequency selection
Soft-PWM operation
240
selection
73
Analog input selection
Terminal 4 input selection
267
74
Input filter time constant
Reset selection/
75
disconnected PU/PU stop
77
Parameter write selection
Reverse rotation prevention
78
selection
Tab. 6-1:
Parameter overview (12)
6 - 12
Incre-
Initial
Setting
ments
Value
Range
1
1
0–15
0
1
1
1
0
1
1
1
10
11
0
1
0
1
2
1
1
0–8
1
14
0–3/14–17
0
1
1
0
2
0
1
1
0
2
Description
PWM carrier frequency can be changed. The
setting displayed is in [kHz]. Note that 0
indicates 0.7 kHz, 15 indicates 14.5 kHz.
Soft-PWM invalid
When Pr. 72 = "0 to 5", Soft-PWM is valid.
Terminal 2 input
Polarity reversible
0–10 V
Not used
0–5 V
0–10 V
With
0–5 V
Terminal 4 input 4 to 20 mA
Terminal 4 input 0 to 5 V
Terminal 4 input 0 to 10 V
The primary delay filter time constant for the
analog input can be set.
A larger setting results in a larger filter.
You can select the reset input acceptance,
disconnected PU (operation panel/FR-PU04/
FR-PU07) connector detection function and
PU stop function. For the initial value, reset
always enabled, without disconnected PU
detection, and with PU stop function are set.
Write is enabled only during a stop
Parameter write is disabled.
Parameter write is enabled in any operation
mode regardless of operation status.
Note:
Parameters that can generally be written
during operation should not be written as well
with this setting.
Both forward and reverse rotations allowed
Reverse rotation disallowed
Forward rotation disallowed
Parameter
All
Para-
Para-
Para-
meter-
meter
meter
Copy
Clear
Refer
Clear
to
Page
✔: Enabled
—: Disabled
6-175
6-177
6-182
6-190
6-195
6-197