Siemens SINAMICS G120 Operating Instructions Manual page 381

Low voltage inverters built-in units with cu250s-2 control units and encoder evaluation
Hide thumbs Also See for SINAMICS G120:
Table of Contents
Exceptions to write protection
Some functions are excluded from write protection, e.g.:
● Activating/deactivating write protection
● Changing the access level (p0003)
● Saving parameters (p0971)
● Safely removing the memory card (p9400)
● Restoring the factory setting
● Transfer the settings from an external data backup, e.g. upload into the inverter from a
memory card.
The parameters that are not write protected are in the List Manual in Section "Parameters for
write protection and know-how protection".
Note
Write protection for multimaster fieldbus systems
Via multimaster fieldbus systems, e.g. BACnet or Modbus RTU, in spite of write protection
being activated, parameters can still be changed. So that write protection is also active when
accessing via these fieldbuses, you must additionally set p7762 to 1.
In STARTER and Startdrive, this setting is only possible using the expert list.
Converter with the CU250S-2 Control Units
Operating Instructions, 04/2018, FW V4.7 SP10, A5E31759476B AG
Saving the settings and series commissioning
7.5 Write protection
379