Mounting the machine control cabinet components

7.4
Mounting the machine control cabinet components
7.4.1

Control cabinet design and cooling

G1 is the only mounting orientation allowed for supply units and drive control-
lers installed in control cabinets.
Table 25: Possibilities of heat dissipation
Closed control cabinet
with air circulation
In the following, the case "control cabinet with fan" is described.
Requirements for control cabinets with fan
● Install filters at the air inlets of the control cabinet to prevent impure air
● Maintain the filters regularly in accordance with the dust load in the sur-
● Change the filters only while the fan is switched off, since otherwise the
Bosch Rexroth AG
Closed control cabinet
with heat exchanger
Impure air in the control cabinet
NOTICE
Risk of damage!
If you operate a control cabinet with fan without the
required filters, devices may be damaged or malfunction
can occur.
from entering the control cabinet.
roundings.
dissolving dirt is aspired by the fan and gets inside the control cabinet.
Control cabinet with fan Closed control cabinet
with air conditioning
unit
RE 62312-B, 03.2022