Storing Sytronix Systems; Storage Conditions; Storage Times - Bosch rexroth Sytronix SvP 7030 IMC Operating Manual

Variable-speed pump drive
Table of Contents
Sytronix SvP 7030 IMC
38 / 186

Storing Sytronix systems

6.3
Storing Sytronix systems
6.3.1

Storage conditions

Table 20: Storage conditions for components to be installed in control cabinets
Designation
Temperature range
Relative humidity
Absolute humidity
Climatic category (IEC721)
Moisture condensation
Icing
Salt mist
Store the products in their original packages in a dry, dust-free, vibration-free
place, and protect them from light and direct solar radiation. Comply with
the classes 1K2, 1B1, 1C1, 1S1, 1M2 specified for storage acc. to DIN EN
60721-3-2.
Table 21: Storage conditions for MPA02
Designation
Temperature range
Relative humidity
Absolute humidity
Moisture condensation
Icing
Salt mist
6.3.2

Storage times

Additional measures must be taken on commissioning to preserve proper func-
tioning – irrespective of the storage time which may be longer than the war-
ranty period of our products. However, this does not involve any additional
warranty claims.
Bosch Rexroth AG
Risk of damage to components from long-term storage!
NOTICE
Some components contain electrolytic capacitors which
may deteriorate during storage.
When storing the following components for a longer
period of time, run them once a year for at least 1 hour: :
Converters and supply units: Operation with mains
voltage U
Inverters and DC bus capacitor units: Operation with
DC bus voltage U
Wet and humidity!
NOTICE
Risk of damage!
Protect the products against moisture with covers.
Store the products exclusively in moisture-proof, dry
rooms.
Symbol
Unit
T
°C
a_store
%
g/m
3
Symbol
Unit
T
°C
a_store
%
g/m
3
LN
DC
Value
-25 ... +55
5 ... 95
1 ... 29
1K3
Not permitted
Not permitted
Not permitted
Value
-20 ... +60
5 ... 95
1 ... 29
Not permitted
Not permitted
Not permitted
RE 62312-B, 03.2022
Table of Contents
loading