Emerson 1420 Reference Manual
Emerson 1420 Reference Manual

Emerson 1420 Reference Manual

Emerson smart wireless gateway reference manual
Hide thumbs Also See for 1420:
Table of Contents

Quick Links

Reference Manual
00809-0200-4420, Rev HC
July 2015
Emerson
Smart Wireless Gateway 1420
Table of Contents
loading

Summary of Contents for Emerson 1420

  • Page 1 Reference Manual 00809-0200-4420, Rev HC July 2015 ™ Emerson Smart Wireless Gateway 1420...
  • Page 3: Table Of Contents

    Reference Manual Contents 00809-0200-4420, Rev HC July 2015 Contents 1Section 1: Introduction Product overview ............1 Using this manual.
  • Page 4 Contents Reference Manual July 2015 00809-0200-4420, Rev HC 4Section 4: Commissioning Overview .............29 System requirements .
  • Page 5 Reference Manual Contents 00809-0200-4420, Rev HC July 2015 Communication specifications ......... .56 A.3.1 Isolated RS485.
  • Page 6 Contents Reference Manual July 2015 00809-0200-4420, Rev HC CAppendix C: DeltaV Ready Overview .............63 Latency considerations in control logic design and operation.
  • Page 7 Read this manual before working with the product. For personal and system safety, and for optimum product performance, make sure you thoroughly understand the Contents before installing, using, or maintaining this product. Within the United States, Emerson Process Management has two toll-free assistance numbers: Global Service Center...
  • Page 8 The products described in this document are NOT designed for nuclear-qualified applications. Using non-nuclear qualified products in applications that require nuclear-qualified hardware or products may cause inaccurate readings. For information on Rosemount nuclear-qualified products, contact your local Emerson Process Management Sales Representative. viii...
  • Page 9: 1Section 1: Introduction

    Reference Manual Section 1: Introduction 00809-0200-4420, Rev HC July 2015 Section 1 Introduction Product overview ® The Smart Wireless Gateway connects WirelessHART self-organizing networks with host ® systems and data applications. Modbus communications over RS-485 or Ethernet LAN provide universal integration and system interoperability. The optional OPC functionality from the Gateway offers a means to connect to newer systems and applications while providing a richer set of data.
  • Page 10: Using This Manual

    Reference Manual Section 1: Introduction 00809-0200-4420, Rev HC July 2015 Using this manual This manual will help to install, configure, operate, and maintain the Gateway. Section 1: Introduction This section introduces the product and describes what components may be found in the box. It also includes details for services and support as well as return and disposal of the product.
  • Page 11: 2Section 2: Configuration

    Reference Manual Section 2: Configuration 00809-0200-4420, Rev HC July 2015 Section 2 Configuration Overview ..............page 3 System requirements .
  • Page 12: Initial Setup

    Reference Manual Section 2: Configuration 00809-0200-4420, Rev HC July 2015 Initial setup Note ™ For information on connecting a Windows 7 PC, see the technical note (document number 00840-0900-4420). 2.3.1 Prepare PC/laptop The PC/laptop will need to be configured to form a private network before communicating to the Gateway.
  • Page 13: Connections And Power

    Reference Manual Section 2: Configuration 00809-0200-4420, Rev HC July 2015 Table 2-1. Default IP Addresses Gateway PC/laptop Subnet Ethernet 1 192.168.1.10 192.168.1.12 255.255.255.0 Ethernet 2 192.168.2.10 192.168.2.12 255.255.255.0 Ethernet 1 (DeltaV Ready) 10.5.255.254 10.5.255.200 255.254.0.0 Ethernet 2 (DeltaV Ready) 10.9.255.254 10.9.255.200 255.254.0.0 2.3.2...
  • Page 14 Reference Manual Section 2: Configuration 00809-0200-4420, Rev HC July 2015 When making physical connections to the Gateway it is important to use the electrical conduit entries located on the bottom of the housing. Connecting through the open terminal block cover (the lower cover) may stress the connections and damage the Gateway.
  • Page 15 Reference Manual Section 2: Configuration 00809-0200-4420, Rev HC July 2015 Figure 2-3. 1420 PoE Jumpering Traditionally Powered Gateway E T H 1 E T H 2 P S E Input Power 10.5V-30V Modbus Case To Host Ethernet 2 Ethernet 1...
  • Page 16: Configure The Gateway

    Reference Manual Section 2: Configuration 00809-0200-4420, Rev HC July 2015 2.3.3 Configure the Gateway It is now possible to log into the Gateway for the first time and begin configuration for placement on a live control network. The following items need to be configured: Security passwords ...
  • Page 17: Time Settings

    Each of the initial passwords for the user accounts is default. It is recommended, for security purposes, that these passwords are changed. The administrator password should be ™ appropriately noted when changed. If it is lost, contact Emerson Process Management for technical support.
  • Page 18 Reference Manual Section 2: Configuration 00809-0200-4420, Rev HC July 2015 Figure 2-4. Time Settings TCP/IP network settings Use caution when making changes to the TCP/IP network settings. If they are lost or improperly configured, it may be impossible to log into the Gateway. Contact the network administrator for information on the proper TCP/IP network settings to apply.
  • Page 19 Reference Manual Section 2: Configuration 00809-0200-4420, Rev HC July 2015 To change the TCP/IP Network Settings: Navigate to System Settings>Gateway>Ethernet Communication. Select Specify an IP address (recommended). Enter the following: Hostname  Domain Name  IP Address  Netmask  Gateway ...
  • Page 20: System Backup

    Reference Manual Section 2: Configuration 00809-0200-4420, Rev HC July 2015 Figure 2-5. Ethernet Settings 2.3.4 System backup The Gateway has a System Backup and Restore feature that saves all user-configured data. It is best practice that a System Backup be performed periodically throughout the installation and configuration process.
  • Page 21: 3Section 3: Installation

    Reference Manual Section 3: Installation 00809-0200-4420, Rev HC July 2015 Section 3 Installation Overview ..............page 13 Mounting .
  • Page 22: Mounting

    Reference Manual Section 3: Installation 00809-0200-4420, Rev HC July 2015 Mounting Find a location where the Gateway has optimal wireless performance. Ideally this will be 15-25 ft. (4,6 - 7,6 m) above the ground or 6 ft. (2 m) above obstructions or major infrastructure. Figure 3-1 shows an example gateway installation.
  • Page 23: Pipe Mount

    Reference Manual Section 3: Installation 00809-0200-4420, Rev HC July 2015 3.2.1 Pipe mount The following hardware and tools are needed to mount the Gateway to a 2-in. pipe: -in. u-bolts (supplied with Gateway)  2-in. mounting pipe  ½-in. socket-head wrench ...
  • Page 24: Remote Antenna (Optional)

    To maintain wireless performance and avoid non-compliance with spectrum regulations, do not change the length of cable or the antenna type. ™ If the supplied remote mount antenna kit is not installed per these instructions, Emerson Process Management is not responsible for wireless performance or non-compliance with spectrum regulations.
  • Page 25 Reference Manual Section 3: Installation 00809-0200-4420, Rev HC July 2015 Figure 3-3. Installation of WL2/WN2 Option A. Control Building E. Lightning Arrestor B. Remote Antenna F. Gateway C. Cable G. Ground D. Drip Loop H. Earth Installation of WL3/WL4 Option (indoor to outdoor applications) Mount the antenna on a 1.5-2 inch pipe mast using the supplied mounting equipment.
  • Page 26 Reference Manual Section 3: Installation 00809-0200-4420, Rev HC July 2015 Figure 3-4. Installation of WL3/WL4 Option A. Control Building E. Lightning Arrestor B. Remote Antenna F. Gateway C. Cable G. Ground D. Drip Loop H. Earth Note: Weather proofing is required! The remote mount antenna kit includes coaxial sealant for the cable connections for the lightning arrestor, antenna, and Gateway.
  • Page 27: Connecting

    Reference Manual Section 3: Installation 00809-0200-4420, Rev HC July 2015 Table 3-1. Remote Antenna Kit Options Kit option Antenna Cable 1 Cable 2 Lightning arrestor Wavelength 50 ft. (15,2 m) Head mount, jack to plug Dipole LMR-400 Gas discharge tube Omni-Directional 0.5 dB insertion loss +6 dB Gain...
  • Page 28: Rs-485

    Reference Manual Section 3: Installation 00809-0200-4420, Rev HC July 2015 Figure 3-6. Terminal Block Diagram 24 VDC (nominal) Serial Modbus Power Input Not Used Not Used Case Ethernet 2 Not Used Not Used Ethernet 2 Ethernet 1 with Power (Covered) (Secondary) (Primary) Figure 3-7.
  • Page 29: Terminating Resistors

    Reference Manual Section 3: Installation 00809-0200-4420, Rev HC July 2015 If the existing data bus uses a 4 wire Full Duplex configuration, see Figure 3-8 to convert to a 2-wire Half Duplex configuration. Figure 3-8. Convert from Full to Half Duplex 3.4.4 Terminating resistors Three DIP switches are provided to enable various terminating resistors to the RS-485 data bus.
  • Page 30: Power

    Reference Manual Section 3: Installation 00809-0200-4420, Rev HC July 2015 Figure 3-10. Typical Half Duplex (2-wire) Network Up to 4000 ft. (1220 m) Device 1 Device 2 Terminators required only for high data Device N rates and long cable (up to 32 runs possible) 3.4.5...
  • Page 31 Reference Manual Section 3: Installation 00809-0200-4420, Rev HC July 2015 In 2003, IEEE 802.3af standard for PoE was adopted. It specified: The wires that would carry power and how  Devices that could source power and devices that could be powered ...
  • Page 32 Reference Manual Section 3: Installation 00809-0200-4420, Rev HC July 2015 In the PoE PD mode, the Gateway draws its power over the selected ethernet cable from another PoE IEEE 802.3 device either 802.3af or 802.3at. Caution is needed in selecting a companion device to the Gateway for PoE. Not all devices labeled PoE will function.
  • Page 33 Does the old 1420 Gateway hardware have PoE? No, not IEEE PoE; in the current 1420 there is a third ethernet port on the far left of the connector board (closest to the hinge). This port has a cover on it; in the manual it is labeled “Ethernet 2 with Power.”...
  • Page 34 How do I know if my 1420 Gateway has IEEE PoE capability? The simplest way to check for IEEE PoE capability is to open the upper door on the 1420 Gateway and the see how the computer board is mounted. In the newer hardware, the board is mounted horizontally.
  • Page 35 July 2015 Are there other changes in the 1420 with the new hardware? Emerson's Quality Policy is to continuously improve our products year after year. The following is a list of some improvements with the new hardware: Ethernet connectors in line with conduit holes ...
  • Page 36 Reference Manual Section 3: Installation 00809-0200-4420, Rev HC July 2015 Installation...
  • Page 37: 4Section 4: Commissioning

    Section 4: Commissioning Reference Manual July 2015 00809-0200-4420, Rev HC Section 4 Commissioning Overview ..............page 29 System requirements .
  • Page 38: Software Installation

    Reference Manual Section 4: Commissioning 00809-0200-4420, Rev HC July 2015 Table 4-3. Supported Operating Systems Operating system Version ™ Windows Professional, Service Pack 3 Windows Server 2003 Standard, Service Pack 2 Windows Server 2003 R2 Standard, Service Pack 2 Windows Server 2008 Standard, Service Pack 2 Windows Server 2008 R2 Standard, Service Pack 1...
  • Page 39: Security Setup Utility

    Reference Manual Section 4: Commissioning 00809-0200-4420, Rev HC July 2015 Note If the autorun function is disabled on the PC, or installation does not begin automatically, double click D:\SETUP.EXE (where D is the CD/DVD drive on the PC) and select OK. Security Setup Utility The Security Setup Utility enables secure communications between the Gateway and host system, asset management software, data historians, or other applications.
  • Page 40: Setup

    Reference Manual Section 4: Commissioning 00809-0200-4420, Rev HC July 2015 4.4.1 Setup In the Security Setup Utility add a new proxy for each Gateway based on the communication protocol that is being used. For example, add an OPC proxy for each Gateway that is communicating OPC.
  • Page 41: Ams Wireless Configurator

    Reference Manual Section 4: Commissioning 00809-0200-4420, Rev HC July 2015 AMS Wireless Configurator AMS Wireless Configurator helps deploy and configure wireless field devices. It provides an ® integrated operating environment that leverages the full capabilities of WirelessHART including embedded data trending, charting, and graphical display capabilities provided by enhanced EDDL technology.
  • Page 42: Licensing And Credits

    Reference Manual Section 4: Commissioning 00809-0200-4420, Rev HC July 2015 Figure 4-3. Wireless Network in the Network Configuration Use the following procedure to configure a HART modem for AMS Wireless Configurator: Open the Network Configuration application. Click Add… Select HART modem and click Install… Click Next.
  • Page 43: 5Section 5: Operation And Maintenance

    ™ ® In accordance with Emerson WirelessHART security guidelines, the Emerson Gateway should be connected to the host system via a LAN (Local Area Network) and not a WAN (Wide Area Network). Network architecture Physical connection types are important when determining the network architecture and what protocols can be used for integration.
  • Page 44 Reference Manual Section 5: Operation and Maintenance 00809-0200-4420, Rev HC July 2015 Figure 5-1. Ethernet LAN Architecture A. Engineering Station D.Controller and I/O B. Primary Control Network E. Smart Wireless Gateway C. Secondary Control Network Fiber optic (optional) A Fiber optic connection supports Modbus TCP, OPC, AMS Wireless Configurator, and HART TCP protocols.
  • Page 45 Reference Manual Section 5: Operation and Maintenance 00809-0200-4420, Rev HC July 2015 RS-485 (serial) An RS-485 connection supports Modbus RTU protocol. Using this connection type, the Gateway is wired to an RS-485 bus which typically leads to a serial I/O card or Modbus I/O card (see Figure 5-3).
  • Page 46: Internal Firewall

    Reference Manual Section 5: Operation and Maintenance 00809-0200-4420, Rev HC July 2015 Internal firewall The Gateway supports an internal firewall that inspects both incoming and outgoing data packets. TCP ports for communication protocols are user configurable, including user specified port numbers and the ability to disable ports. The Gateway’s internal firewall settings can be found by navigating to System Settings>...
  • Page 47: Modbus

    Reference Manual Section 5: Operation and Maintenance 00809-0200-4420, Rev HC July 2015 Modbus The Gateway supports both Modbus RTU over the RS-485 serial port and Modbus TCP over Ethernet. It functions as a sub device on the Modbus network and must be polled by a Modbus master or client (host system).
  • Page 48 Reference Manual Section 5: Operation and Maintenance 00809-0200-4420, Rev HC July 2015 Baud Rate: The data rate or speed of serial communications. This setting is only required for Modbus RTU. Parity: This setting determines parity (none, even, or odd) to use for error checking purposes. This setting is only required for Modbus RTU.
  • Page 49: Register Mapping

    Reference Manual Section 5: Operation and Maintenance 00809-0200-4420, Rev HC July 2015 Use global scale gain and offset?: This setting determines if a global gain and offset is applied for scaled integers or if each value has a unique gain and offset. Unique gain and offsets are found on the Modbus Mapping page.
  • Page 50 Reference Manual Section 5: Operation and Maintenance 00809-0200-4420, Rev HC July 2015 Repeat for each new data point. Select Submit. Address: This is the Modbus RTU address used by the Gateway for this data point. It is possible to group data points assigning them the same address (i.e. all data points from the same process unit can have the same address).
  • Page 51 Reference Manual Section 5: Operation and Maintenance 00809-0200-4420, Rev HC July 2015 Note The **_HEALTHY parameters are a great indication of the health and communications status of the data values. State (state value): The value of a data point which drives a Modbus output of 1. For example, if a data point is reported as either True or False, a state value of True will report a 1 for True and 0 for False.
  • Page 52 Reference Manual Section 5: Operation and Maintenance 00809-0200-4420, Rev HC July 2015 Table 5-2. Predefined Modbus Registers Description Register Data type SYSTEM_DIAG.ADDITIONAL_STATUS_4 49019 8-bit unsigned int SYSTEM_DIAG.ADDITIONAL_STATUS_5 49020 8-bit unsigned int SYSTEM_DIAG.ADDITIONAL_STATUS_6 49021 8-bit unsigned int SYSTEM_DIAG.ADDITIONAL_STATUS_7 49022 8-bit unsigned int SYSTEM_DIAG.ADDITIONAL_STATUS_8 49023 8-bit unsigned int...
  • Page 53: Ethernet/Ip

    Reference Manual Section 5: Operation and Maintenance 00809-0200-4420, Rev HC July 2015 EtherNet/IP Communication settings It is important that the Ethernet/IP communication settings in the Gateway match the setting in the Ethernet/IP master or client. Refer to host system documentation for more information on how to configure these settings or to the reference manual for Ethernet/IP technical document 00809-0500-4420.
  • Page 54 Reference Manual Section 5: Operation and Maintenance 00809-0200-4420, Rev HC July 2015 Table 5-3. System Settings>Protocols>EtherNet/IP Terms Description Assembly Object Type Ethernet/IP use Static assembly object. Ethernet/IP TCP Port The TCP Port used to access Ethernet/IP TCP data directly from the Gateway. Ethernet/IP UDP Ports The UDP Ports used to access Ethernet/IP UDP data directly from the Gateway.
  • Page 55 Reference Manual Section 5: Operation and Maintenance 00809-0200-4420, Rev HC July 2015 Parameter mapping Register Mapping is the process of assigning data points from wireless field devices to Ethernet/IP registers. These registers can then be read by a Ethernet/IP master or client. Ethernet/IP register mapping can be found by navigating to System Settings>Protocols>...
  • Page 56 Reference Manual Section 5: Operation and Maintenance 00809-0200-4420, Rev HC July 2015 Table 5-4. Summary of Terms Used for the Ethernet/IP Mapping Page Terms Description Delete Selected Removes the selected entry from this table Select All Selects all table entries Select None De-selects all table entries Select Errors...
  • Page 57: 6Section 6: Troubleshooting

    Reference Manual Section 6: Troubleshooting 00809-0200-4420, Rev HC July 2015 Section 6 Troubleshooting Service support ............. page 49 Return of materials .
  • Page 58 Reference Manual Section 6: Troubleshooting 00809-0200-4420, Rev HC July 2015 Table 6-1. Troubleshooting Initial Connection Issue Troubleshooting steps Can not find 1. Verify which Ethernet port is being used on the Gateway. Gateway using 2. Verify the IP address for the Gateway (default primary port is 192.168.1.10, Secondary default secondary port is 192.168.2.10).
  • Page 59 Reference Manual Section 6: Troubleshooting 00809-0200-4420, Rev HC July 2015 Table 6-3. Troubleshooting Wireless Field Devices Issue Troubleshooting steps Wireless device 1. Verify the total number of devices on the network (100 max). appears with 2. Go to SETUP > NETWORK > BANDWIDTH and click analyze bandwidth service denied (Note: any changes will require the network to reform) 3.
  • Page 60: Return Of Materials

    2. Reference technical document 00809-0500-4420: Installation manual to connect to an Allen Bradley system. Return of materials ™ To expedite the return process outside of North America, contact your Emerson Process Management representative. Within the United States, call the Emerson Process Management Response Center toll-free number 1 800 654 7768.
  • Page 61 Reference Manual Section 7: Glossary 00809-0200-4420, Rev HC July 2015 Section 7 Glossary This glossary defines terms used throughout this manual or that appear in the web interface of the Smart Wireless Gateway. Term Definition Access Control List A list of all devices that are approved to join the network. Each device will also have a unique join key.
  • Page 62 Reference Manual Section 7: Glossary 00809-0200-4420, Rev HC July 2015 Term Definition Network I.D. Numeric code that associates wireless field devices to the Gateway. This code must be identical in the device and the gateway. Network Manager Operational function within the Smart Wireless Gateway that automatically handles all device connections and scheduling of wireless data.
  • Page 63: Functional Specifications

    Appendix A: Specifications and Reference Data Reference Manual July 2015 00809-0200-4420, Rev HC Appendix A Specifications and Reference Data Functional specifications ........... . . page 55 Physical specifications .
  • Page 64: A.3 Communication Specifications

    Reference Manual Appendix A: Specifications and Reference Data 00809-0200-4420, Rev HC July 2015 Certifications A.4.2 Maximum network size Class I Division 2 (U.S.) 100 wireless devices @ 8 sec. 50 wireless devices @ 4 sec. Equivalent Worldwide 25 wireless devices @ 2 sec. 12 wireless devices @ 1 sec.
  • Page 65: A.6 Dimensional Drawings

    Reference Manual Appendix A: Specifications and Reference Data 00809-0200-4420, Rev HC July 2015 A.6 Dimensional drawings Figure 1. Smart Wireless Gateway 3.51 9.02 (89) (229) 2.81 2.525 2.93 (71,4) (64,14) (74,42) 6.72 (171) 4.78 12.03 (121) (306) 3.08 11.15 (78) (283) 1.59 (40)
  • Page 66: A.6.1 Remote Omni-Antenna Kit

    Reference Manual Appendix A: Specifications and Reference Data 00809-0200-4420, Rev HC July 2015 Figure 2. Remote Omni-Antenna Kit A. Antenna F. 50 ft. (15,2 m) cable B. 20 ft. (6,1 m) cable G. 30 ft. (9,1 m) cable C. 10 ft. (3,0 m) cable H.
  • Page 67: A.7 Ordering Information

    ★ The Standard offering represents the most common options. The starred options (★) should be selected for best delivery. __The Expanded offering is subject to additional delivery lead time. Model Product description 1420 Smart Wireless Gateway Power input ★ 24 VDC Nominal (10.5-30 VDC)
  • Page 68: A.8 Accessories And Spare Parts

    Remote Antenna Kit, 10 ft. (3.0 m) and 40 ft. (12.2 m) cables, Lightning Arrestor (12) High-Gain, Remote Antenna Kit, 25 ft. (7.6m) cable, Lightning Arrestor Typical model number: 1420 A 2 A3 A 2 N5 Single active 10/100 baseT Ethernet port with RJ45 connector. Additional ports disabled.
  • Page 69: B.1 European Directive Information

    RF spectrum. Nearly every country requires this type of product U.S.A. Division 2 ™ Certificate: CSA 70010780 certification. Emerson is working with governmental – Standards: FM Class 3600 2011, agencies around the world to supply fully compliant products –...
  • Page 70: B.5.3 Europe

    Reference Manual Appendix B: Product Certifications 00809-0200-4420, Rev HC July 2015 Special Condition for Safe Use: B.5.5 Brazil 1. Explosion Hazard. Do not disconnect equipment when a INMETRO Type n flammable or combustible atmosphere is present. Certificate: UL-BR 15.0350X Standards: ABNT NBR IEC 60079-0:2008 + Errata B.5.3 Europe 1:2011, IEC 60079-15:2012;...
  • Page 71: Cappendix C: Deltav Ready

    Appendix C: DeltaV Ready Reference Manual July 2015 00809-0200-4420, Rev HC Appendix C DeltaV Ready Overview ..............page 63 Latency considerations in control logic design and operation .
  • Page 72: Requirements

    Reference Manual Appendix C: DeltaV Ready 00809-0200-4420, Rev HC July 2015 Requirements C.3.1 DeltaV Version 10.3 or newer. C.3.2 Smart Wireless Gateway DeltaV Ready option (Data Protocol option 5). See “Ordering information” on page Mounting and connecting Mount the DeltaV Ready Gateway in the same manner as a standard Gateway. (“Mounting”...
  • Page 73: Setup

    Reference Manual Appendix C: DeltaV Ready 00809-0200-4420, Rev HC July 2015 Setup Out of the box the Smart Wireless Gateway is pre-configured for use on the DeltaV control network. In the DeltaV Explore application, the Gateway will automatically appear in the Decommissioned Nodes folder.
  • Page 74 Reference Manual Appendix C: DeltaV Ready 00809-0200-4420, Rev HC July 2015 At this time the Reconcile I/O window will appear. The purpose of this screen is to assign WirelessHART devices to DeltaV I/O channel. This allows the wireless device to be referenced in other DeltaV applications like Control Studio.
  • Page 75 Reference Manual Appendix C: DeltaV Ready 00809-0200-4420, Rev HC July 2015 Figure C-4. Gateway Context Menu (Right Click) Now the Gateway and wireless devices are fully commissioned and available to use in other DeltaV applications. When new devices are added to the wireless network, they will need to be assigned to DeltaV channels through the reconcile process (right click on Gateway and select configure IO).
  • Page 76: Rev Hc July

    Reference Manual Appendix C: DeltaV Ready 00809-0200-4420, Rev HC July 2015 DeltaV Ready...
  • Page 77: Overview

    Appendix D: Redundancy Reference Manual July 2015 00809-0200-4420, Rev HC Appendix D Redundancy Overview ..............page 69 Requirements .
  • Page 78: Setup

    Reference Manual Appendix D: Redundancy 00809-0200-4420, Rev HC July 2015 Setup When configuring redundant Smart Wireless Gateways, it is only necessary to configure one system. The other Gateway will be configured automatically when it is paired with the first Gateway. Choose one Gateway as the starter Gateway.
  • Page 79 Reference Manual Appendix D: Redundancy 00809-0200-4420, Rev HC July 2015 Figure D-2. Redundancy Status After the redundancy system settings have been configured, the two Gateways must be connected and undergo a pairing process. To pair both Gateways and form a redundant system: Connect a PC/laptop to the primary Ethernet port on Gateway A.
  • Page 80 Reference Manual Appendix D: Redundancy 00809-0200-4420, Rev HC July 2015 Figure D-3. Redundancy Setup Connections A. Gateway A D. Primary Ethernet B. Gateway B E. Secondary Ethernet C. PC / Laptop Once the Gateways have finished the pairing process, Gateway A will appear as the current active Gateway on the left hand side and Gateway B will be the standby Gateway on the right (note that left/right hand appearance can be changed on the Redundancy System Settings page).
  • Page 81: Mounting And Connections

    Reference Manual Appendix D: Redundancy 00809-0200-4420, Rev HC July 2015 Mounting and connections Redundant Gateways follow similar mounting and connection practices as a standalone Gateway. Refer to Section 3: Mounting and Connection for more information. In addition to the standard practices, the following considerations should be taken when installing redundant Gateways.
  • Page 82: Simplex Rs-485

    Reference Manual Appendix D: Redundancy 00809-0200-4420, Rev HC July 2015 D.4.3 Simplex RS-485 A simplex RS-485 host connection supports Modbus RTU protocol. When using this architecture, connect the secondary Ethernet port on Gateway A directly to the secondary Ethernet port on Gateway B. Then wire the RS-485 ports for both Gateways in parallel to a single serial card at the host system.
  • Page 83: Dual Rs-485

    Reference Manual Appendix D: Redundancy 00809-0200-4420, Rev HC July 2015 D.4.4 Dual RS-485 A Dual RS-485 host connection support Modbus RTU protocol. When using this architecture, connect the secondary Ethernet port on Gateway A directly to the secondary Ethernet port on Gateway B.
  • Page 84: Diagnostics

    Reference Manual Appendix D: Redundancy 00809-0200-4420, Rev HC July 2015 Diagnostics The redundant system will perform many diagnostic checks to verify the health and connectivity of the system. In the event of a failure, it can take up to 30 seconds for the Gateway to trade positions.
  • Page 85 Reference Manual Appendix D: Redundancy 00809-0200-4420, Rev HC July 2015 Table D-1. Redundancy Diagnostics Parameter Description Data type REDUNDANT_B_MASTER Indication if Gateway B is the active system Boolean REDUNDANT_B_PING Indication if Gateway B is able to ping designated host IP address Boolean REDUNDANT_B_ETH0 Electrical connection status of the primary Ethernet port for Gateway A...
  • Page 86: Gateway Replacement

    Reference Manual Appendix D: Redundancy 00809-0200-4420, Rev HC July 2015 Gateway replacement When replacing or reintroducing a Gateway in a redundant system, always connect both the primary and secondary Ethernet connections before powering the standby Gateway. If the Gateway is being reintroduced (i.e. it was a part of the original redundant system), it will automatically rejoin the redundant system.
  • Page 88 Standard Terms and Conditions of Sale can be found at: 1 Pandan Crescent www.rosemount.com/terms_of_sale. Singapore 128461 DeltaV, SNAP-ON, and the Emerson logo are trademarks and/or service marks of Emerson Electric Co. +65 6777 8211 AMS is a registered trademark of Emerson Process Management.

Table of Contents