Emerson COPELAND F Series User Manual

Emerson COPELAND F Series User Manual

Scroll condensing units for medium and low temperature refrigeration applications
F-series scroll condensing units
For medium and low temperature refrigeration applications
User Manual
Table of Contents
loading

Summary of Contents for Emerson COPELAND F Series

  • Page 1 F-series scroll condensing units For medium and low temperature refrigeration applications User Manual...
  • Page 2: Table Of Contents

    Table of Contents Disclaimer and Safety Information Nomenclature Features Physical Layout of the Unit Pre-Installation Guideline Mechanical Data - 50Hz Mechanical Data - 60Hz Installation, System Processing and Commissioning 11-13 User Operation Maintenance Wiring Diagrams 16-19...
  • Page 3: Disclaimer And Safety Information

    Please do read the following information in this page before proceeding with the rest of the manual. The Emerson™ F-Series refrigeration condensing units should only be installed by suitably qualified and experienced refrigeration technicians. No responsibility can be accepted for damage caused by inexperi- enced or inadequately trained site technicians or improper system design.
  • Page 4 Rapid release of pressurised gas! Personal injuries! Units are factory charged with pressurised dry air to between 1.5 and 2 bar to ensure no ingress of air or moisture during transit. Pressure must be safely reduced prior to fully opening connections or removing blanking components. System breakdown! Personal injuries! Systems without a full charge or with the service valves closed should be electrically locked/tagged if left unattended.
  • Page 5: Nomenclature

    F-Series Scroll Condensing Unit was designed based on key features demanded by industry users: • Wide operating Envelope • Low Applied Cost - Factory Built • Compact design • Optimal layout of components for easy serviceability • Energy efficient silent fans •...
  • Page 6: Features

    Scroll compressor features Dual compliance Compliance means sealing between the orbiting and fixed scroll involutes. Dual compliance means the sealing is on both the axial and radial directions. This prevents refrigerant leak back across successive scroll pressure pockets. Compliance design also allows the scroll involutes to separate in both the radial and axial directions.
  • Page 7: Physical Layout Of The Unit

    Physical Layout of the unit 1. Service valves for customer connection 2. Liquid receiver 3. Scroll compressor 4. HP/LP cutout 5. Junction box Transport and Storage Move F-Series unit only with appropriate mechanical or handling equipment according to weight. Keep in the upright position. Do not stack single boxes on top of each other without pallet in any case.
  • Page 8: Pre-Installation Guideline

    The installation position should be selected with the following points in mind: • Leveling should be +/- 5 mm. • Pipework and electrical connections are readily accessible. • Ensure there are no obstructions in front of the condenser inlet. It is recommended to have a clearance of at least 500mm between the condenser face and adjacent wall or unit.
  • Page 9: Mechanical Data - 50Hz

    Mechanical data - 50Hz Gross Condensing unit Compressor model weight model (kg) FMV9A-ZB 58-TFM ZB58KQE-TFD-551 1294 1329 FMV9A-ZB 66-TFM ZB66KQE-TFD-551 1294 1329 FMV6A-ZB 66-TFM ZB66KQE-TFD-551 1294 1329 FMV6A-ZB 76-TFM ZB76KQE-TFD-551 1294 1329 FMV6A-ZB 95-TFM ZB95KQE-TFD-551 1294 1329 FMC8A-ZS 09-PFZ ZS09KAE-PFJ-600 444.04 FMC8A-ZS 09-TFM ZS09KAE-TFD-600...
  • Page 10: Mechanical Data - 60Hz

    Mechanical data - 60Hz Gross Description Compressor model weight (kg) FMH8A-ZB 15-TF7 ZB15KQE-TF7-559 679.5 FMM8A-ZB 19-TF7 ZB19KQE-TF7-559 707.04 FMM8A-ZB 21-TF7 ZB21KQE-TF7-559 707.04 FMR6A-ZB 26-TF7 ZB26KQE-TF7-559 1095 1130 FMR7A-ZB 29-TF7 ZB29KQE-TF7-559 1095 1130 FMS9A-ZB 38-TF7 ZB38KQE-TF7-559 1095 1130 FMV6A-ZB 58-TF7 ZB58KQE-TF7-551 1294 1329 FMV6A-ZB 66-TF7...
  • Page 11: Installation, System Processing And Commissioning

    Installation, System processing and commissioning Utmost care must be taken while handling the scroll condensing unit. Please go through the contents below to ensure proper handling: Leak test, evacuation, and charging The following assumes the condensing unit to be leak-free on arrival. That is an important step before proceeding with the following.
  • Page 12 Leak test (by nitrogen pressure) Release nitrogen from system. Start vacuum pump and open main pump valve. Evacuation Note that the following procedure is based upon achieving an actual system vacuum stan-dard and it is NOT TIME- DEPENDENT! Step-by-Step: Check suction capability of the vacuum pump with a gauge before commencing evacuation process.
  • Page 13 In cooler ambients, it may be necessary to run the compressor in order to complete charging. IMPORTANT! TO BE CLEARLY UNDERSTOOD PRIOR TO RUNNING ANY SCROLL COMPRESSOR Scroll compressor systems should be charged as quickly as possible by bleeding liquid refrigerant into the suction line with the compressor running.
  • Page 14: User Operation

    Unit Operation Before starting the unit, ensure the following: • All the electrical connections are correct and as per the recommended wiring diagrams • All low side tubings are properly insulated • Leak check is done and unit is pre-charged with refrigerant through high side •...
  • Page 15: Maintenance

    Maintenance Condenser Fins Condenser fins become dirty over time as ambient air is induced to the condenser. Dirty coil surfaces result in high condensing temperatures and poor unit performance. Regular cleaning is recommended with frequency depending on the installation and the surrounding environment. As a general guide, it is advisable to do this at least once every two months.
  • Page 20 About Emerson Emerson (NYSE: EMR), headquartered in St. Louis, Missouri (USA), is a global technology and engineering company providing innovative solutions for customers in industrial, commercial, and residential markets. Emerson Commercial and Residential Solutions business helps ensure human comfort and health, protect food quality and safety, advance energy efficiency, and create sustainable infrastructure.

This manual is also suitable for:

Copeland fmv9a-zb 58-tfmCopeland fmv9a-zb 66-tfmCopeland fmv6a-zb 66-tfmCopeland fmv6a-zb 76-tfmCopeland fmv6a-zb 95-tfmCopeland fmc8a-zs 09-pfz ... Show all

Table of Contents