ZX Condensing Unit
ZX Condensing Unit
User Manual
User Manual
Table of Contents
loading

Summary of Contents for Emerson COPELAND ZX Series

  • Page 1 ZX Condensing Unit ZX Condensing Unit User Manual User Manual...
  • Page 2: Table Of Contents

    Table of Contents Disclaimer Features and Benefits Nomenclature Bill of Material Physical Layout of the Unit Product Specification Qualified Refrigerants And Oils CoreSense ™ for ZX Platform Condensing Unit Network Wiring Installation Condensing Unit Handling Location and Fixing Refrigeration Piping Installation ZXL Liquid Line Insulation Brazing Recommendations Expansion Valve Selection...
  • Page 3: Disclaimer

    Disclaimer Thank you for purchasing the ZX platform condensing unit from Emerson Climate Technologies. ZX platform CDUs are the best in class within the capacity and operating range available in the market. ZX CDU is designed to operate reliably and to deliver high operating efficiencies in medium and low temperature refrigeration applications.
  • Page 4: Nomenclature

    Intelligent Store Better Decision Making Highest Effi ciency Lower Energy Bills Reliability Lower Maintenance Cost ZX and ZXL Family Variable Speed Fan Proprietary electronic algorithms present advantage on diagnose, communication, and protection purposes. They are also fundamental Motor and High to control fan speed, optimizing Energy Performance for Local Effi ciency Fan Blade Seasonal Ambient Temperatures...
  • Page 5: Physical Layout Of The Unit

    Physical Layout of the Unit The following figures give an introduction to the physical layout of the ZX Platform CDU CoreSense ™ Scroll Compressor Adjustable LP Controller Figure 2. CoreSense and other components in ZX Platform CDU ™ Accumulator Oil Separator (Optional in MT CDU) Liquid Receiver Liquid Sight Glass/ Moisture Indicator...
  • Page 6: Product Specification

    Product Specification For application envelope, envelope varies according to applications and refrigerants. Please refer to ZX platform product catalogue, product manual, or Copeland™ Brand Products Selection Software. Qualified Refrigerants and Oils Refrigerant R448 / R449 / R407F / R404A Emkarate RL 32 3MAF / R507 / R134a / R22 Mobil EAL Artic 22 CC Oils are pre-charged in both compressor and oil separator.
  • Page 7 Keyboard Descriptions - Single Button Display target set point; In programming mode, select a parameter or confirm an operation. Hold for 5 seconds to reset any lockouts if the current state of the controller allows for it to be Start Reset reset.
  • Page 8 ZXD Unit Setting Point Modification Step Action Phenomenon and Description Press SET button for 3 seconds, the measurement units (°C ) will flash together. Press“ ” > 3 seconds Modify the number Press “ ” or “ ” Press“SET” to confirm, the number will flash for 2 seconds (or wait for about 10 second Press “...
  • Page 9 Adjusting condensing temperature set-point Step Action Phenomenon and Description Enter menu to select “PAr” (parameter) or “rtC” Press “ ” + Select “PAr (parameter)” Press “ ” or “ ” Press “ ” Browse to t18 parameter Press “ ” or “ ”...
  • Page 10 Quick Access Menu Browse - Sensors Status and Actual Values Step Action Phenomenon and Description Enter quick access menu, will display“P1P”(Press “Up” or “Down” to view other sensors Press “ ” View the actual value of “P1P” Press “ ” Press “...
  • Page 11 Exact Timing of the Alarm Step Action Phenomenon and Description Display “SEC” Press “ ” Display “A01” Press “ ” Display alarm code in “A01” Press “ ” Display “Hr” Press “ ” Display the alarm exact timing: hour Press “ ”...
  • Page 12: Network Wiring

    Download the Program from Hot-Key to Controller Step Action Phenomenon and Description Turn-off the controller Insert Hot-Key The “doL” message will blink followed a by a flashing “End” label (Note: if display “Err”, Turn-on the controller it means it fails to download program to the controller. Please restart the process.) Controller will restart working with the new parameters after 10 seconds Remove Hot-Key Network Wiring...
  • Page 13 Termination Resistor for XWEB300D If XWEB300D is placed at the beginning or at the end of the line, please install its termination resistor by adding a jumper in position 2 (JMP2 on the back side of the unit). Do not add the jumper if XWEB300D is placed in the middle of the RS485 line. Dixell XWEB300D Configuration For CoreSense XWEB300D is compatible with ZX CDU if XWEB has the library of ZX controller CoreSense (controller) model.
  • Page 14: Installation

    Installation Copeland ZX condensing units are delivered with a holding charge of neutral gas. The condensing unit should be located in such a place to prevent any dirt, plastic bag, leaves or papers from covering the condenser and its fins. The unit must be installed without restricting the airflow.
  • Page 15: Location And Fixing

    Location and Fixing The unit should always be installed in a location that ensures clean air flow. It is recommended that a clearance of 300 mm from the wall (or the next unit) be maintained from the unit’s left and rear panels whereas a clearance of 500 mm must be maintained from the unit’s right, top and front panels (seen facing the front of the unit).
  • Page 16: Refrigeration Piping Installation

    Refrigeration Piping Installation All interconnecting pipes should be of refrigeration grade, clean, dehydrated and must remain capped at both ends until installation. Even during installation, if the system is left for any reasonable period of time (say two hours), pipes should be re- capped to prevent moisture and contaminants from entering the system.
  • Page 17 Note: For the ZXD Units, we recommend using Alco Electronic Expansion Valves (EXV). The selection of the EXV will depend on the load profile on the ZXD Unit. Please contact your local Emerson Climate Technologies office for assistance on selection.
  • Page 18: Electrical Connection

    Electrical Connection Power Supply The ZX condensing unit electrical connection to the power supply must be made by qualified technicians, who should refer to the electrical diagrams located inside the electric connection panel. The units are designed for below power supply at ± 10% voltage tolerance.
  • Page 19: Start Up And Operation

    REMINDER: Do not use the system compressor as a vacuum pump and do not operate the compressor while the system is in vacuum. Emerson Climate Technologies recommends Triple Evacuation Process (best practice) to be implemented on all our installations. Step-by-step: 1.
  • Page 20 Refrigerant Charging Reminder ∙ The scroll compressor design requires system charging with liquid refrigerant into the liquid line. ∙ Do not vapor charge the ZX Scroll unit. After ensuring all valves are opened and system is vacuumed properly, only then start the refrigerant charging process Step-by-step: 1.
  • Page 21: Controller Initialization Message

    Controller Initialization Message Step Action Phenomenon and Description Power on controller All LEDs will light up for 3 seconds. Firmware version will be displayed for 3 seconds. Parameter setting file (bin file number) identifier will be displayed for 3 seconds. Normal display (actual suction temperature will be displayed on ZXD unit, condensing temperature will be displayed on ZX/ZXL unit) Bin Files Number Range...
  • Page 22 Refrigerants Step Action Phenomenon and Description Enter menu to select “PAr” (parameter) or “rtC” Press “ ” + “ ” Select“PAr (parameter)” Press “ ” or “ ” Press “ ” Browse to parameter C07 Press “ ” or “ ”...
  • Page 23 Jumper received with the unit Jumper after installation Jumper to be installed Change the condensing temperature setpoint (E39) from 20°C to 35°C for R134a operation as below Step Action Phenomenon and Description Enter menu to select “PAr” (parameter) or “rtC” Press “...
  • Page 24: Alarm Codes

    Alarm Codes Level Descriptions Unit (including compressor) is running but some data reach Warning unsafe area; alarm dry-contact will not close; reset automatically Unit (including compressor) may run not with full functions; alarm dry-contact will not close; reset Alarm automatically Lock Unit (including compressor) stops working;...
  • Page 25 Alarm Description Possible Reason Action Reset Code Electrical Error One or two phases of compressor Missing phase alarm power supply lost or Voltage sensors The compressor will be tripped Automatically with time delay do not work (3-ph unit only) Missing phase alarm happened The compressor will be tripped Press “Start”...
  • Page 26 Alarm Description Possible Reason Action Reset Code Refrigeration system error Automatically when HP switch High pressure switch alarm High pressure switch is open The compressor will be tripped closes High pressure switch alarm happens The compressor will be tripped Press “Start” >5 sec or manually High pressure switch lock frequently and the unit will be locked...
  • Page 27: Wiring Diagrams

    Wiring Diagrams 2/T1 1/L1 4/T2 3/L2 6/T3 5/L3 F2(4A/250V) F3(4A/250V) To Fan GNYE ELECTRONIC EXPANSION VALVE ZXD-TF7 R22 ONLY SENSOR AMBIENT DISCHARGE SENSOR DLT COND. SENSOR MID COIL PRESSURE TRANSDUCER...
  • Page 29 2/T1 1/L1 4/T2 3/L2 6/T3 5/L3 F2(4A/250V) F3(4A/250V) To Fan GNYE ELECTRONIC EXPANSION VALVE ZX ONLY SENSOR AMBIENT PHE SENSOR VAPOR-OUT ZXL ONLY PHE SENSOR VAPOR-IN ZXL ONLY DISCHARGE SENSOR DLT COND. SENSOR MID COIL...
  • Page 31 2/T1 1/L1 4/T2 3/L2 6/T3 5/L3 F2(4A/250V) F3(4A/250V) To Fan GNYE ELECTRONIC EXPANSION VALVE SENSOR AMBIENT PHE SENSOR VAPOR-OUT ZXL/ZXB ONLY PHE SENSOR VAPOR-IN ZXL/ZXB ONLY DISCHARGE SENSOR DLT COND. SENSOR MID COIL...
  • Page 32: System Start-Up And Operation Check Sheet

    System Start-Up and Operational Check Sheet Client Details Facility/Customer Name : Address : Contact Details : Installer : Installation Date : ZX Condensing Unit Info CDU Model : Serial Number : CDU Location : Indoor Unit Make/Model : System Details System Operation Room/Case ID : COMP Voltage :...
  • Page 33 Products, specifications, and data in this literature are subject to change without notice. The information given herein is based on data and tests which Emerson Climate Technologies believes to be reliable and which are in accordance with today’s technical knowledge. It is intended for use by persons having the appropriate technical knowledge and skill, at their own discretion and risk.
  • Page 34 Tel : +27 11 451 3700 Fax: +27 11 451 3800 EmersonMEA EmersonMiddleEastAfrica EmersonClimateMEA.com Emerson, Copeland Performance Alert, CoreSense and Copeland Scroll are trademarks of Emerson Electric Co. or one of its affiliated companies. ©2019 Emerson, Inc. All rights reserved.

Table of Contents