Pe Connection, Power Supply Unit And Neighboring Device - Bosch Rexroth IndraDrive HMV01.1E-W0030 Project Planning Manual

Supply units
Hide thumbs Also See for Rexroth IndraDrive HMV01.1E-W0030:
Table of Contents
7-20
Electrical Installation

PE Connection, Power Supply Unit and Neighboring Device

Tightening Torque
The PE connection (grounding) to the drive controller can be provided in
duplicate in the case of the drive controllers through:
• a grounding bracket on the front (see figure below)
• the rear panel of the device if the devices are positioned against a
shared, bare metal surface
Note:
You must use the grounding bracket on the front for ground
connection in any case. The rear panel of the device can be
used in addition.
1: Grounding bracket for ground connection
Fig. 7-14: PE connection to supply unit resp. neighboring device
Note:
If cables are used for PE connection they must have a cross
section of at least 10 mm
smaller than the cross section of the mains supply cable.
The grounding bracket is fixed to the supply unit with screws (M6 x 25)
Design
6 Nm
Rexroth IndraDrive
1
erdungslasche_hmv
2
. The cross section must not be
DOK-INDRV*-HMV-*******-PR01-EN-P
Table of Contents
loading