Bosch Rexroth AG
Instructions for Use
5.2.2

X2 Terminal Block

Terminal
Function
Terminal block X2 (RJ12), RS485/RS232 at the top of the device
(1) RS485 A
Data cable RS485
(2) RS485 B
(3) GND
Reference potential of the
bus signals
(4) 232 TXD
Data cable RS232
(5) 232 RXD
(6) +5V
5V power supply
5.2.3

X3, Mains Connection (PE, L1, L2/N, L3)

General Information

LSA Control S.L. www.lsa-control.com [email protected] (+34) 960 62 43 01
Rexroth IndraDrive Fc Drive Controllers Frequency Converters FCS01
AGND and DGND are common reference potentials for analog or
digital inputs. If applicable, 5V/15V can be picked off by several
terminals. The sum of the picked-off currents must not exceed
250 mA/150 mA.
Data
Baud rate
9600... 38400 Baud
0V digital
Baud rate
9600... 38400 Baud
5V, ± 20%, 250 mA
Fig.5-4:
X2 Terminal Block
The frequency converter does not require any specific kind of fusing at the
power input side. We recommend that you use the usual mains fuses and a
main switch or contactor.
See also chapter 3 "Technical Data"
230V devices of up to 2.2 kW may either be operated with 1-phase 230V (L/N
= L1/L2) or with 3-phase 230V (L1/L2/L3).
All 400V devices and devices ≥ 3 kW must only be supplied with 3-phase
mains voltage (L1/L2/L3).
Fig.5-5:
Mains Connection
DOK-INDRV*-FCS01******-IT01-EN-P
Description / suggested wiring
RJ12: Pin 1...6
Parame‐
ters
P502...
P513