technical bulletin
When the E2 is at one end of the daisy chain, terminate the E2 with all three jumpers in the
terminated (UP) position.
RS485 MODBUS
CONNECTORS
Document Part # 026-4909 Rev 1 20-OCT-2011
©2011 Emerson Climate Technologies, Inc. This document may be photocopied for personal use.
Visit our website at http://www.emersonclimate.com/ for the latest technical documentation and updates.
Installation Instructions: XJ Scroll Condenser to E2
+485
Figure 2 - E2 Modbus Connected to the One-Way Communication Board
E2 Power Interface
Board (PIB)
0V
-485
WHITE
-485
SHIELD
0V
+485
BLACK
ECT MODBUS
CONNECTOR on the
XJ Scroll One-way
Comm Board
D0: RS485- (A)
C:
Common
D1: RS485+ (B)
Page 3 of 13