Table 11-4 Trip conditions
Trip
C.rtg
SMARTCARD trip: The voltage and/or current rating of the source and destination drives are different
Drive rating dependent parameters (parameters with the RA coding) are likely to have different values and ranges with drives of
different voltage and current ratings. Parameters with this attribute will not be transferred to the destination drive by SMARTCARDs
when the rating of the destination drive is different from the source drive and the file is a parameter file. However, with software
V01.09.00 and later drive rating dependent parameters will be transferred if only the current rating is different and the file is a
differences from default type file.
Press the red
Drive rating parameters are:
Parameter
4.05/6/7, 21.27/8/9
186
5.07, 21.07
5.09, 21.09
5.10, 21.10
5.17, 21.12
5.23, 21.13
5.24, 21.14
5.25, 21.24
The above parameters will be set to their default values.
C.Typ
SMARTCARD trip: SMARTCARD parameter set not compatible with drive
Press the red
187
Ensure destination drive type is the same as the source parameter file drive type

Table 11-5 SMARTCARD status indications

Lower display
boot
A parameter set is being transferred from the
SMARTCARD to the drive during power-up. For further
information, please refer to section 11.2.4 Booting up
from the SMARTCARD on every power up (Pr 11.42 =
boot (4)) .
154
System
Mechanical
Electrical
Getting
Installation
Installation
Started
reset button
2.08
Standard ramp voltage
Current limits
4.24
User current maximum scaling
Motor rated current
Motor rated voltage
Rated power factor
Stator resistance
5.18
Switching frequency
Voltage offset
Transient inductance
Stator inductance
6.06
DC injection braking current
6.48
Line power supply loss ride through detection level
reset button
Description
www.controltechniques.com
Basic
Running
SMARTCARD
Optimization
parameters
the motor
operation
Diagnosis
Function
Lower display
cArd
The drive is writing a parameter set to the SMARTCARD
during power-up.
For further information, please refer to section
11.2.3 Auto saving parameter changes (Pr 11.42 = Auto
(3)) .
Onboard
Advanced
Technical
Diagnostics
PLC
parameters
Data
Description
Unidrive SPM User Guide