Figure 6-37 Parallel Rectifier Control Terminals And - Emerson Unidrive SPM User Manual

Variable speed ac drive
Table of Contents
Safety
Product
Introduction
Information
Information
configuration
6.14.2
SPMC/U Hardware configuration - Multiple
Rectifier modules
Figure 6-37 Parallel rectifier control terminals and descriptions
Fan control
0V common
Status input 0
0V common
Status input 1
0V common
External 24V
supply
0V common
Status output 0
0V common
Status output 1
0V common
Rectifier OK
Relay contacts
6.14.3
Unidrive SPMC/U control connections
Status input connections
70
0V common
71
Status input 1
72
0V common
73
Status input 0
Function
Logic 0 voltage level
Logic 1 voltage level
Open circuit voltage level
Input resistance
Fan control connections
74
0V common
75
Fan control
Function
Voltage range
Input threshold
Input resistance
Unidrive SPM User Guide
Issue Number: 3
System
Mechanical
Electrical
Getting
Installation
Installation
Started
SPMC/U 1
75
74
73
72
71
70
85
84
83
82
81
80
91
90
To allow status monitoring for
applications using more than one
rectifier
<8.4V
>8.4V
-4.8V source resistance 8.7k
Ω
15k
The internal fan in the rectifier is
controlled by a temperature control
loop. The fan can be forced to run
at full speed by connecting this
terminal to +24V
0V to 24V supply voltage +2V
10V
Ω
6.8k
www.controltechniques.com
Basic
Running
SMARTCARD
Optimization
parameters
the motor
operation
75
74
73
72
71
70
85
84
83
82
81
80
91
90
Inverter (master)
60
61
62
63
Status output connections
80
0V common
81
Status output 1
82
0V common
83
Status output 0
Function
Logic 0 voltage level
Logic 1 voltage level
Source resistance
N
NOTE
When a system contains paralleled Unidrive SPMC/Us, the rectifier's
status outputs must be daisy chained to the status inputs of the next.
Providing the system is fused correctly, the method used to monitor the
rectifier status must have the ability to disable the system within 500ms.
A PLC can be used to monitor the status output of the rectifier. PLC input
impedance must be no greater than 10kΩ. Status signals are not
latched.
84
0V common
Function
Onboard
Advanced
Technical
PLC
parameters
Data
SPMC/U 2
Fan control
0V common
Status input 0
0V common
Status input 1
0V common
External 24V
supply
0V common
Status output 0
0V common
Status output 1
0V common
Rectifier OK
Relay contacts
SPMD
0V common
Status 1 input
0V common
Status 0 input
Provides status monitoring from
the rectifier to the connecting drive
/ monitoring equipment to trip the
rectifier unit
0V
24V supply voltage
1k1
Common connection for all external
devices
UL Listing
Diagnostics
Information