13. Special conditions of use
a. The user is to ensure the probe assembly is installed in such a way to
prevent any damage due to impact or ignition source due to friction.
b. Under certain extreme circumstances, a non-standard paint on the
enclosure of the Rosemount 2120 may generate an ignition-capable level of
electrostatic charge. Therefore, the Rosemount 2120 shall not be installed
in a location where the external conditions are conducive to the build-up of
electrostatic charge on such surfaces. Additionally, the Rosemount 2120
shall only be cleaned with a damp cloth.
c. The user is to ensure the ambient air temperature (Ta) and the process
temperature (Tp) are within the range detailed above for the T class of the
specific flammable gases or vapors present.
d. The user is to ensure the ambient air temperature (Ta) and the process
temperature (Tp) are within the range detailed above for the maximum
surface temperature of the specific flammable dusts present.
10.14 Instructions for hazardous area installations (I1 and I7)
Model numbers covered:
2120***H*I1**, 2120***K*I1**
2120***H*I7**, 2120***K*I7*
("*" indicates options in construction, function and materials)
The following instructions apply to the equipment covered by certificates
numbered
Sira 05ATEX2130X and IECEx Sir 06.0070X
1. The Intrinsically Safe approved versions of the 2120 may be used in a
hazardous area with explosive gases and vapors with apparatus groups IIC, IIB,
and IIA, and with temperature classes T1, T2, T3, T4, and T5 [
1, and 2].
The temperature class of the installation will be determined from the higher of
the process or ambient temperature.
2. The equipment may be used in a hazardous area with explosive dusts with
apparatus groups IIIC, IIIB, and IIIA [
The maximum surface temperature of the installation will be determined from
the higher of the process or ambient temperature.
3. It is a special condition of the certification that the temperature of the
electronics housing is in the range of –50 to +80 °C.
It must not be used outside this range. It will be necessary to limit the external
ambient temperature if the process temperature is high.
See also "Technical data" below.
4. Suitably trained personnel shall carry out installation in accordance with the
applicable code of practice.
5. The user should not repair this equipment.
6. If the equipment is likely to come into contact with
the responsibility of the user to take
being adversely affected, thus ensuring that the type of protection is not
compromised.
24
:
in Zones 20, 21, and 22].
IECEx:
aggressive substances
suitable precautions
December 2016
in Zones 0,
IECEx:
, it is
that prevent it from