Bosch Rexroth ctrlX CORE X7 Operating Instructions Manual page 22

Table of Contents
22 / 50
Interface description
EtherCAT process data
The bus coupler and the ctrlX CORE are provided with data that is inserted into the cyclic process
image. This data length is 5 words in total. According to the EtherCAT standard, this data before the
input process data is shown in the process image.
The process data words 0...3 contain the voltage and current values of U
consumption of the infeed terminal and the I/O modules) as well as their bits for the supply voltage
diagnostics. This information can also be retrieved via acyclic services using CoE. These are shown as
the indices 6000, 6010 and 6020 hex.
Word 0
Word 1
Word 2
Word 3
Word 4
0
1
2
3
4
5
6-15
Diagnostic strategy
Mechanisms
Different mechanisms are used for the diagnostics.
Mechanism
EtherCAT state machine
EtherCAT hardware watchdog
Diagnostic objects in the CoE object directory
10F1
Diagnosis history object
10F3
Bosch Rexroth AG
U
Voltage
P
U
Current
P
U
Voltage
L
U
Current
L
(Only the current consumption of the infeed terminal (typ. 50 mA) and the
I/O modules (3 A max.) is measured. In addition to the transferred measured
value, the ctrlX CORE
PLUS
U
Undervoltage
P
U
Overvoltage
P
U
Overcurrent
P
U
Undervoltage
L
U
Overvoltage
L
U
Overcurrent
L
Reserved
consumes more than shown here.
Diagnostics
EtherCAT system diagnostics
Extended diagnostics, e.g. peripheral errors
Error settings
20 diagnostic messages can be stored
Diagnosis history
ctrlX CORE X7
and U
(only the current
P
L
R911419122, Edition 01