Panasonic Eco Solutions Nordic AB
MEW01472
Rev: -
9.2.3
Planning Instructions Fire alarm system EBL512 G3, United version 2.7.x
(This front also holds one extra LED & two extra push
buttons.).
The unit shall run in S/W mode 1736 – 1587. Up to 1200 m
cable can be used.
description MEW00224.

External Presentation Units

1728 External Presentation unit (EPU). A compact size enclosure
(HxWxD, 145 x 220 x 50 mm) made of grey high impact ABS.
Fitted with a supplementary "O" ring gasket, it will comply
with IP61, in respect of dust and moisture. The unit has no
door, i.e. the front is accessed directly, when required. The
push buttons are disabled until they are supposed to be used.
The unit shall be wall mounted. Two compression glands are
attached. The front's designation texts are in Swedish. This
unit is intended for pre-warning, co-incidence
smoke / heat) alarm presentation. If there are two or more
alarms in the system, you can scroll amongst them but the fire
alarms cannot be reset via this unit.
All or selected alarms will be presented in a display (alpha-
numeric LCD, 2x40 characters), with back-light. An alarm text
will also be presented together with each alarm, if programmed
in Win512 version 2.7.x. Furthermore, at least 617 texts can for
selected fire alarms be stored in the unit and will in such a case
be shown, instead of the texts sent out from EBL512 G3 for
these alarms. These text messages will be downloaded to the
unit via Win512 version 2.7.x.
Any fault in the system will be presented as "General fault in
system". The buzzer will sound.
disablement in the system will be presented as "General
disablement in system".
A built-in buzzer will sound like in EBL512 G3. The buzzer
can be silenced but the alarm devices in the installation cannot
be silenced via this unit.
downloaded directly in the unit. The unit is power supplied
from EBL512 G3 or an external power supply. The unit shall
run in S/W mode 1728 – 1587.
The number of units that can be power supplied via EBL512 G3
(or an external power supply) is depending on all other units
connected to the same c.i.e. / external power supply. Up to
1200 m cable can be used. For more information, see Technical
description MEW00290.
47
Two zone / address dependence.
For more information, see Technical
46
It can be silenced. Any
46
New software versions can be
56
47