Planning Instructions Fire alarm system EBL512 G3, United version 2.7.x
 Disable by door in any control unit or any external FBP:
Door open in any C.U. or any ext. FBP will disable the outputs
for routing equipment (Fire brigade and fault tx) in all C.U:s.
In the display (or via menu H4/U1) is shown (xx = C.U. number):
Fire alarm routing disabled

National holidays

Up to twenty national holidays can be set for the whole system.
each national holiday the Year (2001-2038), Month (01-12) and Day
of the Month (01-31) has to be set. "Add" to or "Delete" from the
Date list. "Annual repetition" can be set if a holiday returns the same
date every year. (The year will be deleted for these days.)
Function: Normally the Day of week 1-7 ON/OFF times are valid. A
national holiday has higher priority, i.e. the Day of week 8 ON/OFF
times are valid for this day instead of the normal times.

Alarm algorithms

For each analog detector programmed (via Win512 version 2.7.x) is
an alarm algorithm selected (and when required an alternative alarm
algorithm).
A number of algorithm "Properties" are displayed under this tab.
Detector type, Logical and Short names can be changed. The Short
name (< six characters) is shown in menu H4/U4. Level 1 or Level 2
can be selected (see chapter "Win512 Tools menu", page 110):
In Level 1 it is also possible to change: The pre-warning and the
heavy smoke / heat alarm algorithm parameters for smoke and heat
detectors.
In Level 2 (a special password is required) it's also possible to change:
The fire alarm algorithm parameters for smoke and heat detectors.

Classic smoke detectors' properties

NOTE! 2200+2210, 2202+2210 & AUT cannot be used in EBL512
G3 United version 2.7.x.
Detector:
2300(ION)
2210(ION2) = ION2200
2304(OPT)
2210(OPT2) = OPT2202
AUT
Logical name: Classic
Short name: Class
Algorithm parameters: Default values, see table:
117
NOTE! ON/OFF times for each time channel (1-14) and day of week = 8
(national holiday) have to be set in the "Time channels" tab.
137
(by open door in CU xx)
117
For