Planning Instructions Fire alarm system EBL512 G3, United version 2.7.x
"technical address", etc. to be read also when the detector is
plugged in its base. 100 label holders per packet. Excl. labels.
3391 Labels for 3390. A packet with self-adhesive white labels for
label holder 3390. 10 A4-sheets à 132 labels for laser printer
usage. The print-out is done via Win512 version 2.7.x.

Addressable I/O units

3361 Addressable multipurpose I/O unit.
COM loop. The unit has two programmable inputs:
Monitored input
....used as zone line input (Z) (terminals 6 & 7): End-of-line
capacitor 470 nF mounted in the last unit on the zone line.
Short circuit on the line can generate a fault or a fire alarm (set
via Win512 version 2.7.x).
conventional detectors.
Max. 1.5 mA. Cable: Max. 50 ohms and max. 50 nF.
....used as general input (In0) (terminals 5 & 7): An input for
NC or NO contacts (set via Win512 version 2.7.x).
Isolated input (In1) (terminals 8 & 9): An optocoupler input
(external 24 V DC / 8 mA is required). Normally low or high
(set via Win512 version 2.7.x).
The unit has two programmable relay
Relay output (Re0): NC or NO contacts (set via Win512
version 2.7.x).
Relay output (Re1): Like Re0.
Connections and examples, see drawings 512G3 - 31 & - 36.
Unit dimensions: (L x W x H) 90 x 70 x 32 mm.
A plastic protection cover is attached. The cover dimensions:
(L x W x H) 129 x 73 x 45 mm.
3361 is intended to be surface mounted and for indoor use in
dry premises. When required, the unit can be mounted in a
Waterproof (IP66 / 67) box (3362).
indicate communication "OK" or alarm condition. For more
information, see the Product Leaflet. The COM loop address is
set with the Address setting tool (3314). The unit has an
33
The same physical unit (3361) is also used for Fan control together with
the Fan control panel 4593. Then it has a separate dialog box in Win512
version 2.7.x.
34
Via Win512 version 2.7.x it is possible to define this input to function like
a manual call point ("Used as MCP"), i.e. it will not be collectively disabled
via menu "Disable zone, H2/B1", can not be included in two-unit
dependence, it can not use the "alarm delay" function and it can not be
disabled via a time channel.
35
Relay contacts: max. 2 A @ 30 V DC / 125 V AC.
33
Power supplied via the
This input is intended for
34
35
outputs:
3361 has an LED to
46