2-Zone / 2-Address Dependence (Co-Incidence Alarm); 2-Zone Dependence - Panasonic EBL512 G3 Planning Instructions

Fire alarm system
Hide thumbs Also See for EBL512 G3:
Table of Contents
Panasonic Eco Solutions Nordic AB
MEW01472
Rev: -
16.9
16.9.1
Planning Instructions Fire alarm system EBL512 G3, United version 2.7.x
2-zone / 2-address dependence (Co-
incidence alarm)
In some premises 2-zone or 2-address dependent fire alarm ("Two unit
dependent" in Win512 version 2.7.x) can be used to avoid unwanted /
false alarms (nuisance alarms). A time channel can turn on/off this
function.

2-zone dependence

Each zone in the system can be programmed to be "Two zone
dependent" for fire alarm activation. The zone has to belong to one of
ten "Two zone dependent" groups (1-10).
Function:
Two or more zones in the same group have to be in "fire alarm state"
at the same time to activate fire alarm in the control unit. When only
one of the zones is in "fire alarm state" it is indicated in the control
unit (c.i.e.) as follows:
The buzzer sounds like for pre-warning (0.8 / 5 sec.).
In the c.i.e. LCD the following information is shown:
Co-incidence alarm
ZZZ
User definable alarm text.
Menu
Programmable outputs can be activated by trigger condition "Two
Zone Dependent Fire Alarm" but no other outputs will be activated.
86
See also chapter "Two zone dependence", page 140.
87
Fire alarm state is when a fire alarm normally would have been activated
in the c.i.e.