Win512 Tools Menu - Panasonic EBL512 G3 Planning Instructions

Fire alarm system
Hide thumbs Also See for EBL512 G3:
Table of Contents
Panasonic Eco Solutions Nordic AB
MEW01472
Rev: -
16.31
Planning Instructions Fire alarm system EBL512 G3, United version 2.7.x
NOTE 2! The text "Menu" above the soft key (P4) is visible in the
display only if the door in the c.i.e. is open, while the text "Evacuate" /
"Evacuate off" above (P7) is always visible in the current conventions.

Win512 Tools menu

Figure 24 .
Win512 version 2.7.x "Tools" menu.
commands can be disabled (e.g. if you are not connected or not
logged on).
The "Tools" menu is used, when the PC is connected to an EBL512
version 2.7.x control unit for e.g. download / backup of SSD.
NOTE! The PC cannot be connected to an EBL512 G3 United
version 2.7.x control unit.
Validate:
The SSD is validated (EN54 violations, warnings and
system errors).
Communication: Log on / Log off to the EBL512 unit.
Synchronize:
(When connected and logged on to an EBL512.)
Synchronization of control units (same data in all control units) and
Win512 version 2.7.x.
Upgrade Loop Units: To upgrade 33xx detectors to NORMAL mode
(one at a time or all on one COM loop at the same time). NOTE!
This is not valid for an EBL512 G3 United version 2.7.x control unit.
Report: Prints out a "Zone-Address  Output" list or a "Time
channel  Zone-Address" list.
Download: (When connected and logged on to an EBL512 unit.) For
download of SSD to one or more EBL512 and EBL512 G3 units in a
mixed system.
Backup: (When connected and logged on to an EBL512 unit.) For
backup (upload) of SSD from all the EBL512 units.
SSD verify: (When connected and logged on to an EBL512.) The
Win512 version 2.7 SSD is compared to the EBL512 SSD.
110
Some

Hide quick links:

Table of Contents
loading

Table of Contents