Programmable Voltage Outputs (S0-S3); Programmable Relay Outputs (R0-R1); Programmable Inputs (I0-I3) - Panasonic EBL512 G3 Planning Instructions

Fire alarm system
Hide thumbs Also See for EBL512 G3:
Table of Contents
Panasonic Eco Solutions Nordic AB
MEW01472
Rev: -
5.3
5.4
5.5
Planning Instructions Fire alarm system EBL512 G3, United version 2.7.x

Programmable voltage outputs (S0-S3)

The 24 V DC outputs are supervised (monitored)
according to dwg 512 G3 – 23. When all connections are done a
calibration has to be performed, see chapter "Calibration of supervised
outputs", page 105 and the EBL512 G3 Operating Instructions
MEW01473, chapter "Calibration of supervised outputs (menu
H5/A1)".
Each output has to be programmed (via Win512 version 2.7.x)
regarding:
 Type of output, i.e. output for Control, Alarm devices, etc.
 Logic, i.e. normally low (default) or normally high (24 V DC)
 Activation time and type (steady, pulse, delay, etc.).
 Control expression (one or more trigger conditions).
See also chapter "Programmable outputs", page 64.

Programmable relay outputs (R0-R1)

Connections according to dwg 512 G3 – 23.
Each output has to be programmed (via Win512 version 2.7.x)
regarding:
 Type of output, i.e. output for Control, Alarm devices, etc.
 Logic, i.e. normally open (NO) or normally closed (NC) contacts.
 Activation time and type (steady, pulse, delay, etc.).
 Control expression (one or more trigger conditions).
See also chapter "Programmable outputs", page 64.

Programmable inputs (I0-I3)

Connections according to dwg 512 G3 – 23.
Each input has to be programmed (via Win512 version 2.7.x)
regarding:
 Trigger condition (Triggered by).
 Logic, i.e. normally open (NO) or normally closed (NC) contacts.
 Additional information, depending on the selected trigger
condition (Fault no., Zone, Address, Fault message (Error text),
etc.)
Open = R > 20K. Closed = R < 500 .
An input has to be activated > 0.5 sec.
See also chapter "Programmable inputs", page 60.
7
The outputs are in Win512 version 2.7.x default set as supervised but via
Win512 version 2.7.x it is possible to set each output (S0-S3) individually to
be not supervised.
8
A normally high output is not supervised.
25
7
.
Connections