1MRS756800 F
4.8.1
630 series
Engineering Manual
IEC09000395 V1 EN
Figure 30:
Import exported CID file for created generic IED
Using a 630 series IED as a generic 61850 device supports controlling switch gears,
monitoring measured values and reading disturbance recordings.
Enabling Web Server
The Web Server has to be separately enabled for parametrization from COM600. Set
the parameters in SAB600.
1.
In the Web Server Enabled box, type True.
2.
In the Web Server IP Address box, type the IP address.
IEC09000396 V1 EN
Figure 31:
Enable Web Server for parametrization
The Web Server option becomes available in the COM600 Substation view and
it opens the WHMI for the 630 series IED.
IEC09000397-1-en.vsd
IEC09000397 V1 EN
Figure 32:
WEB Server available in COM600 substation view
IEC09000395-1-en.vsd
IEC09000396-1-en.vsd
Section 4
Setting up a project
51