Configuring Dnp3 Class - ABB Relion 630 Series Engineering Manual

Hide thumbs Also See for Relion 630 Series:
Table of Contents
1MRS756800 F
9.4.1
630 series
Engineering Manual
2.1. Click in the class field of the signal to change the class configuration.
The Select Class window opens.
2.2. Make the selection according to the definitions in the project and click OK
to close the window and get the new configuration.
IEC08000338 V2 EN
Figure 109:

Configuring DNP3 class

In DNP3 the user classifies the signals and defines which signals are not a member of
any class. Communication Management tool has a default predefined organization of
classes per signal type. In the master station the classes can be polled in sequences
according to the demands in the project. Unsolicited reporting is possible as well.
Modify the organization of the classes for each signal individually.
1.
Click in the Class field of the signal.
The Select Class window opens for classifying the signal.
2.
Select the signal classes and choose between None and 0 to 3 according to the
project demands.
3.
Click OK to set the signal classification.
4.
Write to IED.
DNP3 communication engineering
IEC08000338-2-en.vsd
CMT: Select Class window
Section 9
135