Reengineering; Reengineering In The Application Configuration Tool; Reengineering In The Parameter Setting Tool - ABB Relion 630 Series Engineering Manual

Hide thumbs Also See for Relion 630 Series:
Table of Contents
1MRS756800 F
10.2
10.2.1
10.2.2
630 series
Engineering Manual
Collect the order code information for the migrated configurations before starting the
license update.
1.
Save and close Application Configuration tool when the configuration
migration is completed.
2.
Run License Update tool from the IED context menu.
3.
Optionally, create a backup of the IED before starting the license.
This is not required if a backup of the project has been created earlier.
4.
Select online or offline mode for migration.
In the online mode, the order code information is read from the IED. In the
offline mode, the user can paste the order code from the clip board or select the
options manually.
5.
Select order options for the IED and finish the process.
The new license also comprises the optional software used in the
original configuration.

Reengineering

Reengineering in the Application Configuration tool

Review reported changes in a migration report and in an output log window. If a
function has been removed, it indicates that the function has been replaced by another
function or the migration has not been possible for other reasons. If a signal has been
removed, it indicates that the particular signal has a new functional meaning. Study the
technical manual to ensure how the functions are used correctly. Even if the function
has a new version number, the actual change in the function itself might be very minor.
See
Table 4
for list of functions that might require actions after the migration.
1.
In the Application Configuration tool, update the configuration for the listed
functions.
2.
Save the configuration.
3.
Run Validate Configuration.
4.
Examine the report in the log window, and update the configuration
accordingly.
5.
Save the Application Configuration tool configuration again and exit.

Reengineering in the Parameter Setting tool

Parameter values remain unchanged for all the functions listed in Versioned
Functions and Hardwares or Functions instance is changed due to change in
creation rule. Parameter values remain unchanged also for the functions not listed in
Section 10
Configuration migration
139
Table of Contents
loading

Table of Contents