Section 7
IEC 61850 communication engineering
7.3.2
106
GUID-466A9F09-C384-48A7-B38C-B5BF221F416E V1 EN
Figure 78:
IEC 61850: Export SCD step 1
2.
Right-click the station and select Export.
3.
Select a location from the open standard Windows menu to store the file and
name it.
4.
The SCL Export Options dialog box opens.
GUID-4779D0DE-FAEF-4B27-835E-8C1FD2215FE6 V1 EN
Figure 79:
IEC 61850: SCL Export Options
5.
Select Export Private Sections and click Export to export the private sections
to the SCD file. A progress window shows the ongoing export of the station.
Exporting ICD or CID files
1.
Select the IED in the Plant Structure view.
2.
Right-click the IED and select Export...
The Export dialog box opens.
3.
From the Save as type list, select the type of file to export.
•
Configured IED description (.cid) for the IEC 61850 structure as needed
for the IED at runtime
•
IED capability description (.icd) for the IEC 61850 structure
Station
IEC08000415.vsd
IEC09000627-1-en.vsd
1MRS756800 F
630 series
Engineering Manual