RCB client configuration with IET600

To succeed with an RCB client configuration, the potential clients and their
communication configuration should be known. Therefore, the IEDs must be added
and configured to the subnetwork before configuring the RCB client.
The rows of the RCB client editor show IEDs and RCBs and the columns show the
available client IEDs.
If a client IED is not on the same subnetwork as a server IED or RCB,
it cannot be configured as a client.
GUID-E295D590-217A-41E6-8C99-2B76E432325C V1 EN
Figure 95:
RCB client editor
Different keys can be used when editing the cells.
PLUS SIGN (+), asterisk (*) or X to add an additional client to the existing ones
Numbers to change the client sequence or add clients
MINUS SIGN (-), SPACEBAR or DELETE to delete existing clients
Double-clicking with the mouse to add or delete clients
RCB client editor supports both manual and semi-automatic client configuration.

Configuring RCB clients semi-automatically

On the right in the RCB client editor there are option buttons to choose whether to
show IEDs (for defining default clients) or RCBs or both together.
There are also buttons to allow semi-automatic configuration of default clients and
RCB clients.
IEC 61850 communication engineering
Section 7
123