Siemens SIPART Series Operating Instructions Manual page 94

Electropneumatic positioners with and without hart
Hide thumbs Also See for SIPART Series:
Table of Contents
Connection
5.1 Electric
3. Loosen screw
4. Then, secure the loose ribbon cable (B) on the wall of the rack as shown in the following
graphic. To do this, use the cable tie (A) supplied with the EMC filter module
C73451-A430-D23.
5. Secure the EMC filter module using the screw
6. Fit the basic electronics
7. Insert the ribbon cable connector
electronics.
8. In non-hazardous environment:
– Stick the supplied nameplate over the nameplate on the external position detection
– Replace the blue cable gland
Refer to section "Scope of delivery of external position detection system (Page 265)", items
"Nameplate for device version without explosion protection" and "Gray cable gland".
For further information on fitting of an option module, refer to the operating instructions of the
respective positioner version in section "Installing/mounting > Installing option modules".
Procedure for connecting an external position detection system
1. Connect the three terminals of the external position detection system
terminals of the EMC filter module
2. Tighten the cable glands
See also
Installing optional modules in the standard and intrinsically safe version (Page 49)
92
in the connection area of the positioner.
(A)
Cable tie
system
.
(B)
back into the positioner.
of the EMC filter module onto the positioner basic
by the supplied gray cable gland.
using a cable as shown in the wiring diagram.
and
.
Ribbon cable connector
loosened in the third step.
SIPART PS2 with and without HART
Operating Instructions, 10/2013, A5E00074631-11
to the three
Table of Contents
loading

This manual is also suitable for:

Sipart ps2 series

Table of Contents