Siemens SIPART Series Operating Instructions Manual page 211

Electropneumatic positioners with and without hart
Hide thumbs Also See for SIPART Series:
Table of Contents
Overview of diagnostics values
No.
Abbreviation
1
STRKS
2
CHDIR
3
CNT
4
A1CNT
5
A2CNT
6
HOURS
7
WAY
8
TUP
9
TDOWN
10
LEAK
11
PST
12
PRPST
13
NXPST
14
DEVI
15
ONLK
16
STIC
17
ZERO
18
OPEN
19
PAVG
20
P0
21
P100
22
IMPUP
23
IMPDN
24
DBUP
25
DBDN
26
SSUP
27
SSDN
28
TEMP
29
TMIN
30
TMAX
31
T1
32
T2
33
T3
SIPART PS2 with and without HART
Operating Instructions, 10/2013, A5E00074631-11
Meaning
Number of strokes
Number of changes of direction
Number of fault messages
Number of alarms 1
Number of alarms 2
Operating hours
Determined actuator travel
Travel time up
Travel time down
Leakage
Monitoring of the partial stroke test
time since the last partial stroke test
time until the next partial stroke test
General control valve fault
Pneumatic leakage
Stiction
Zero point displacement
Displacement of upper end stop
Position average
Potentiometer value of lower end stop (0%)
Potentiometer value of upper end stop (100%) 0.0 ... 100.0
impulse length up
impulse length down
deadband up
deadband down
slow step zone up
slow step zone down
Current temperature
Minimum temperature ("min/max pointer")
Maximum temperature ("min/max pointer")
Number of operating hours in temperature
range 1
Number of operating hours in temperature
range 2
Number of operating hours in temperature
range 3
Alarm, error, and system messages
Values that can be
displayed
0 ... 4.29E9
0 ... 4.29E9
0 ... 4.29E9
0 ... 4.29E9
0 ... 4.29E9
0 ... 4.29E9
0 ... 130
0 ... 1000
0 ... 1000
P 0.0 ... 100.0
OFF / ###.#, fdini, notSt,
SdtSt, fdtSt, notd, Strt,
StoP
###, notSt, Sdtst, fdtSt
OFF / ###
OFF, 0.0 ... 100.0
OFF, 0.0 ... 100.0
OFF, 0.0 ... 100.0
OFF, 0.0 .. 100.0
OFF, 0.0 ... 100.0
0.0 ... 100.0
0.0 ... 100.0
6 ... 160
6 ... 160
0.1 ... 10.0
0.1 ... 10.0
0.1 ... 100.0
0.1 ... 100.0
-50 ... 100
-58 ... 212
-50 ... 100
-58 ... 212
-50 ... 100
-58 ... 212
0 ... 4.29E9
0 ... 4.29E9
0 ... 4.29E9
10.2 Diagnosis
Unit
Reset
possible
-
X
-
X
-
X
-
X
-
X
Hours
-
mm or °
-
s
-
s
-
%
-
s for ###.#
-
Days
-
Days
-
%
-
-
-
%
-
%
-
%
-
%
-
%
-
%
-
ms
-
ms
-
%
-
%
-
%
-
%
-
° C
-
° F
-
° C
-
°F
° C
-
° F
Hours
-
Hours
-
Hours
-
209
Table of Contents
loading

This manual is also suitable for:

Sipart ps2 series

Table of Contents