Messages during initialization
Message
Line
Up
Down
P--
X
RUN1
X
RUN2
X
RUN3
X
RUN4
X
RUN5
X
YEND1
X
YEND2
X
RANGE
X
ok
x
SIPART PS2 with and without HART
Operating Instructions, 10/2013, A5E00074631-11
Meaning / cause
Measuring range was exceeded, the
potentiometer is in the inactive zone, the
transmission ratio selectors or the effective
lever arm are not adjusted as per the
actuator travel
Initialization was started, part 1 is active (the
direction of action is determined)
Initialization part 2 is active (actuator travel
check and determination of end stops)
Initialization part 3 is active (determination
and display of travel times)
Initialization part 4 is active (determination of
the minimum controller increment length)
Initialization part 5 is active (optimization of
the transient response)
The first end position can be approached
only in case of a manual initialization
The second end position can be approached
only in case of a manual initialization
The end position or the measuring span is
beyond the permissible measuring range
only in case of a manual initialization
The permissible measuring range of end
positions is achieved only in case of a
manual initialization
Alarm, error, and system messages
10.1 Output of system messages in the display
Remedy
Switch the transmission ratio selector to
90° especially in case of part-turn
actuators
Adjust the effective lever length of linear
actuators as per the measuring range
Maintenance
Maintenance
Maintenance
Maintenance
Wait until "FINSH" is displayed
(initialization completed successfully)
Acknowledge by pressing the operating
mode button briefly and exit the
configuration level by pressing it longer
Approach the first end position using the
"+" or "-" button
Acknowledge using the operating mode
button
Approach the second end position using
the "+" or "-" button
Acknowledge using the operating mode
button
Approach another end position using the
"+" and "-" buttons and acknowledge with
the operating mode button, or
Move the friction clutch until "ok" is
displayed, and then acknowledge with
the operating mode button, or
Terminate the initialization process by
pressing the operating mode button,
switch to the P-manual mode and correct
the actuator travel and the position
displacement sensor
Acknowledge with the operating mode
button; the remaining steps ("RUN1" to
"FINSH") execute automatically