7.5 Commissioning part-turn actuators
3. Call the "2.YAGL" parameter. To do this, briefly press the
already been set to 90° automatically. The display shows the following:
4. Call the "4.INITA" parameter. To do this, briefly press the
the following:
5. Start the initialization process. To do this, press the
the display shows the following:
The positioner runs through five initialization steps during the automatic initialization
process. Displays for the initialization steps from "RUN1" to "RUN5" are shown in the
lower line on the display. The initialization process depends on the actuator used, and
takes up to 15 minutes.
6. The following display indicates that the automatic initialization is complete. The total angle
of rotation of the actuator is shown on the upper line on the display:
Aborting the automatic initialization process
1. Press the
The positioner is in the "Configuration" mode.
2. Exit the "Configuration" mode. To do this, press the
The software status is displayed.
After releasing the
is not initialized.
134
button. The display shows the following:
button, the positioner is in "P manual mode". The part-turn actuator
button. This parameter has
button. The display shows
button for at least 5 seconds until
button for at least 5 seconds.