Siemens SIPART Series Operating Instructions Manual page 182

Electropneumatic positioners with and without hart
Hide thumbs Also See for SIPART Series:
Table of Contents
Parameterizing/addressing
9.4 Description of parameters
b4.FACT2 - factor 2
Use this sub-parameter to set the factor for the formation of limit threshold 2. Set the factor in
a range from "0.1" to "100.0". The limit threshold is the product of "b2.LIMIT" and
"b4.FACT2".
The threshold 2 fault message is displayed when the limit threshold 2 is exceeded. The
process to activate and display this fault message is described in the "XDIAG" parameter.
The factory setting is "10.0".
b5.FACT3 - factor 3
Use this sub-parameter to set the factor for the formation of limit threshold 3. Set the factor in
a range from "0.1" to "100.0". The limit threshold is the product of "b2.LIMIT" and
"b5.FACT3".
The threshold 3 fault message is displayed when the limit threshold 3 is exceeded. The
process to activate and display this fault message is described in the "XDIAG" parameter.
The factory setting is "15.0".
180
SIPART PS2 with and without HART
Operating Instructions, 10/2013, A5E00074631-11