FR-D700 SC EC
PS
PU Stop
Stop with the STOP/RESET key of the PU is set in Pr. 75 "Reset selection/disconnected
PU detection/PU stop selection". (For Pr. 75, refer to section 6.16.1.)
Check for a stop made by pressing the STOP/RESET key of the operation panel.
Turn the start signal off and release with PU/EXT key.
RB
Regenerative brake prealarm
Appears if the regenerative brake duty reaches or exceeds 85% of the Pr. 70 "Special
regenerative brake duty" value. When the setting of Pr. 70 "Special regenerative brake
duty" is the initial value (Pr. 70 = 0), this warning does not occur.
If the regenerative brake duty reaches 100%, a regenerative overvoltage (E. OV ) occurs.
The RBP signal can be simultaneously output with the [RB] display. For the terminal used
for the RBP signal output, assign the function by setting "7 (positive logic) or 107 (negative
logic)" in any of Pr. 190, Pr. 192 or Pr. 197 "Output terminal function selection". (Refer to
section 6.9.5.)
Check that the brake resistor duty is not high.
Check that the Pr. 30 "Regenerative function selection" and Pr. 70 "Special regenerative
brake duty" values are correct.
Increase the deceleration time (Pr. 8).
Check the Pr. 30 "Regenerative function selection" and Pr. 70 "Special regenerative
brake duty" values.
TH
Electronic thermal relay function prealarm
Appears if the cumulative value of the Pr. 9 "Electronic thermal O/L relay" reaches or
exceeds 85% of the preset level. If it reaches 100% of the Pr. 9 "Electronic thermal O/L
relay" setting, a motor overload trip (E. THM) occurs. The THP signal can be simultane-
ously output with the [TH] display. For the terminal used for THP signal output, assign the
function by setting "8 (positive logic) or 108 (negative logic)" in any of Pr. 190, Pr. 192 or
Pr. 197 "Output terminal function selection"). (Refer to section 6.9.5.)
Check for large load or sudden acceleration.
Is the Pr. 9 "Electronic thermal O/L relay" setting is appropriate? (Refer to section 6.7.1.)
Reduce the load weight or the number of operation times.
Set an appropriate value in Pr. 9 "Electronic thermal O/L relay". (Refer to section 6.7.1.)
MT
Maintenance signal output
Indicates that the cumulative energization time of the inverter has reached a given time.
When the setting of Pr. 504 "Maintenance timer alarm output" set time is the initial value
(Pr. 504 = 9999), this warning does not occur.
The Pr. 503 "Maintenance timer" setting is larger than the Pr. 504 "Maintenance timer
alarm output set time" setting. (Refer to section 6.20.3.)
Setting "0" in Pr. 503 "Maintenance timer" erases the signal.
Causes and corrective actions
FR-PU04
PS
FR-PU07
FR-PU04
RB
FR-PU07
FR-PU04
TH
FR-PU07
FR-PU04
FR-PU07
7 - 7