When offline auto tuning ends, press the STOP/RESET key of the operation panel during PU op-
eration. For external operation, turn off the start signal (STF signal or STR signal) once. This op-
eration resets the offline auto tuning and the PU's monitor display returns to the normal indica-
tion. (Without this operation, next operation cannot be started.)
If offline auto tuning ended in error (see the table below), motor constants are not set. Perform
an inverter reset and restart tuning.
Pr. 96 Setting
Tab. 6-10: Parameter 96 setting
When tuning is ended forcibly by pressing the STOP/RESET key or turning off the start signal
(STF or STR) during tuning, offline autotuning does not end normally. (The motor constants
have not been set.) Perform an inverter reset and restart tuning.
When using the motor corresponding to the following specifications and conditions, reset Pr. 9
"Electronic thermal O/L relay" as below after tuning is completed.
● When the rated power specifications of the motor is 200/220V (400/440V) 60Hz, set 1.1
times rated motor current value in Pr. 9.
● When performing motor protection from overheat using a PTC thermistor or motor with
temperature detector such as Klixon, set "0" (motor overheat protection by the inverter is
invalid) in Pr. 9.
When you know motor excitation current (no load current), set the value in Pr. 82.
FR-D700 SC EC
Error Cause
8
Forced end
9
Inverter protective function operation
Current limit (stall prevention) function was
91
activated.
Converter output voltage reached 75% of
92
rated value.
– Calculation error
93
– A motor is not connected.
Selection and protection of a motor
Remedy
Set "11" in Pr. 96 and perform tuning again.
Make setting again.
Set "1" in Pr. 156.
Check for fluctuation of power supply voltage.
Check the motor wiring and make setting
again.
Set the rated current of the motor in Pr. 9.