Monitor Menu (1 of 2)
This Monitor Menu displays items that are not specific to one boiler.
Item Field
Access: ADV
Access: ADV
Access: ADV
Access: ADV
Access: ADV
Access: ADV
Access: ADV
Access: ADV
Access: ADV
Access: ADV
Access: ADV
Heatronic 4000
Range
ENERGY
Total calculated energy being delivered to the load since this item was last cleared.
0 to 65535 Therms
Press & hold the 'CLEAR' button while viewing to reset. Requirements: This
item is only available when Flow Sensor is set to ON & a boiler return sensor is
connected.
PRIMARY PUMP 1 RUN TIME
0 to 65535 hours
The total running time of primary pump 1 since this item was cleared. Press &
hold the 'CLEAR' button while viewing to reset.
PRIMARY PUMP 2 RUN TIME
0 to 65535 hours
The total running time of primary pump 2 since this item was cleared. Press &
hold the 'CLEAR' button while viewing to reset.
DHW PUMP RUN TIME
0 to 65535 hours
The total running time of the DHW Tank pump since this item was cleared. Press
& hold the 'CLEAR' button while viewing to reset.
-22 to 266°F
PRIMARY SUPPLY HIGH
(-30.0 to 130.0°C)
Records the highest primary supply temperature since this item was last cleared.
Press & hold the 'Clear' button while viewing to reset.
-22 to 266°F
PRIMARY SUPPLY LOW
(-30.0 to 130.0°C)
Records the lowest primary supply temperature since this item was last cleared.
Press & hold the 'CLEAR' button while viewing to reset.
PRIMARY RETURN HIGH
-22 to 266°F
Records the highest primary return temperature since this item was last cleared.
(-30 to 130°C)
Press & hold the 'CLEAR' button while viewing to reset.
Requirements: This item is only available when a primary return sensor is
connected.
PRIMARY RETURN LOW
-22 to 266°F
Records the lowest primary return temperature since this item was last cleared.
(-30.0 to 130.0°C)
Press & hold the 'CLEAR' button while viewing to reset.
Requirements: This item is only available when a primary return sensor is
connected.
SUPPLY TEMPERATURE DIFFERENCE HIGH
-22 to 266°F
Records the highest temperature difference between the primary supply &
primary return sensors since this item was cleared. Press & hold the 'CLEAR'
(-12.0 to 148.0°C)
button while viewing to reset.
Requirements: This item is only available when the primary supply & primary
return sensors are connected
FLOW RATE HIGH
0 to 65535 gpm
Records the highest flow rate from the flow sensor since this item was last cleared.
Press & hold the 'CLEAR' button while viewing to reset.
Requirements: This item is only available when Flow Sensor is set to ON.
PRESSURE HIGH
0 to 65535 psi
Records the highest pressure since this item was last cleared. Press & hold the
'CLEAR' button while viewing to reset.
Requirements: This item is only available when Pressure Sensor is set to ON.