Testing The Control Wiring - Bosch Heatronic 4000 Installation & Operating Instructions Manual

4 boiler control, dhw, bacnet and modbus io heatronic 4000 2014/04 en-us
Hide thumbs Also See for Heatronic 4000:
Table of Contents

Testing the Control Wiring

Testing the Power
If the control display does not turn on, check the Power In L & N terminals (83 & 84) using an electrical multimeter. The voltage
should measure between 103.5 to 126.5 V (ac).
User Test (HAND)
The User Test (HAND mode) is one of the Manual
Override modes of the control. Refer to the Hand
mode for a description of the steps that are included
Manual
to operate the outputs. The steps are dependent
Override
how the boiler(s) (Source # Menu) & the system
(Setup menu) are configured.
Testing the Auxiliary Relay ---------- -------- ------ ------
Activate the HAND mode within the Manual Override. Select the
Auxiliary item & set it to ON. Using an electrical meter, measure
for continuity between the Auxiliary terminals (43 & 44).
Testing the Alert Dry Relay ------------------------------
Activate the HAND mode within the Manual Override. Select
the Alert item & set it to ON. Using an electrical meter, measure
for continuity between the Alert Dry terminals (45 & 46).
Testing the Primary Pumps ----------------------- -------
Activate the HAND mode within the Manual Override.
For primary pump 1, select the Primary Pump item & set it
to PMP1. Using an electrical meter, measure for continuity
between the Primary Pump 1 terminals (47 & 48).
For primary pump 2, select the Primary Pump item & set it
to PMP2. Using an electrical meter, measure for continuity
between the Primary Pump 2 terminals (49 & 50).
Testing the DHW Tank Pump ------------- -------- -------
Activate the HAND mode within the Manual Override. Select
the DHW Pump item & set it to ON. Using an electrical
meter, measure for continuity between the DHW Tank Pump
terminals (85 & 86).
Testing the Boiler Pump(s)
Activate the HAND mode within the Manual Override. Select
the Boil 1 PUMP item & set it to ON. Using an electrical meter,
measure for continuity between the Boiler 1 Pump terminals
(75 & 76). Repeat the steps above for Boiler Pumps 2, 3 & 4.
Testing the Central Heat (CH) Call
Set the Application Mode to RSET. Remove all wires from
the CH Call terminals (5 & 6). The control display should
show no Heat Call. Reconnect wires. Then apply either a
Testing the DHW Tank Call
Set the Application Mode to either RSET, SETP or EMS.
Remove all wires from the DHW Tank Call terminals (7 & 8).
The control display should show no DHW Call. Reconnect
Testing the Fuel Switch
Set the Application Mode to either RSET, SETP or EMS.
Remove all wires from the Fuel Switch terminals (9 & 10).
The control display should show no F SW. Reconnect wires.
Heatronic 4000
------------------------------
------------------------------
------------------------------
----------------------------
Testing the Boiler Stage(s) --- --- ------ --- --- --- --- --- ----
T hi s test applies for single stage & two stage boilers only.
Activate the HAND mode within the Manual Override. For a
single stage boiler, select the Boil STG item & set it to 1.
Using an electrical meter, measure for continuity between the
Boiler 1 Stage 1 terminals (53 & 54).
For a two stage boiler, select the Boil STG item & set it to 1.
Using an electrical meter, measure for continuity between the
Boiler 1 Stage 1 terminals (53 & 54). Set the Boil STG item to 2.
Using an electrical meter, measure for continuity between the
Boiler 1 Stage 2 terminal (55 & 56). Repeat the steps above,
as applicable, for Boilers 2, 3 & 4.
Testing the Modulating Boiler Output - --- --- - --- --- --- --
This test applies for modulating boilers only.
Activate the HAND mode within the Manual Override.
Select the Boil 1 MOD item & set a desired firing rate. Using
an electrical meter, measure for either a V (dc) or mA signal
between the Boiler + Mod - terminals (51 & 52). The reading
should be between 0 V (dc) & 10 V (dc) or 4 mA & 20 mA.
Repeat the steps above for Boilers 2, 3 & 4.
Testing the Temperature Boiler Output - --- ----- --- ---- - -
This test applies for EMS boilers only. Activate the HAND
mode within the Manual Override.
Select the Boil 1 TEMP item & set a desired temperature
between 50 & 210°F (10 & 99°C). Using an electrical
meter, measure for a V (dc) signal between the Boiler +
Mod - terminals (51 & 52). The reading should be between
0 V (dc) & 10 V (dc). Repeat the steps above, as applicable,
for Boilers 2, 3 & 4.
short circuit or 24 V (ac) over the CH Call terminals. The
control should now show a Heat Call.
wires. Then apply either a short circuit or 24 V (ac) over the
DHW Tank Call terminals. The control should now show a
DHW Call.
Then apply either a short circuit or 24 V (ac) over the Fuel
Switch terminals. The control should now show a F SW.
30 of 60
Terminals 83 & 84
Manual Override Button
--- --- --- --- --- --- --- --- --- ----
-- --- --- --- --- --- --
- --- -- - ---- --- --- -
Terminals 5 & 6
Terminals 7 & 8
Terminals 9 & 10
BTC461503101C | 6720810369 (2018/03)