Setup Menu (5 of 6)
Item Field
Access: ADV
Access: ADV
Access: ADV
Access: ADV
Access: ADV
Access: ADV
Access: ADV
Access: ADV
Access: ADV
Access: ADV
BTC461503101C | 6720810369 (2018/03)
Range
INDIRECT DHW BOILER COUNT
1 to 4
Selects the number of boilers to be used when only a DHW Tank Call is
present.
Default: 2
Requirements: This item is only available when Application Mode is set to RSET,
SETP or EMS, Indirect DHW Mode is set to ON & Indirect DHW Location is set
to Boil.
60 to 220°F
SETPOINT OCCUPIED TEMPERATURE
The boiler target temperature when a Central Heat (CH) Call is present during
(15.5 to 104.0°C)
the occupied periods.
Default: 180°F (82.0°C)
Requirements: This item is only available when Application Mode is set to
SETP.
SETPOINT UNOCCUPIED TEMPERATURE
OFF, 60 to 220°F
The boiler target temperature when a Central Heat (CH) Call is present during the
(15.5 to 104.0°C)
unoccupied periods. If operation is not desired during the unoccupied periods,
Default: OFF
select OFF.
Requirements: This item is only available when Application Mode is set to SETP
& the Setback / Off switch is set to Setback
70 to 190°F
DEDICATED DHW OCCUPIED SETPOINT
(21.0 to 88.0°C)
The temperature of the dedicated DHW tank during the occupied periods.
Default: 140°F (60.0°C)
Requirements: This item is only available when Application Mode is set to
DDHW.
OFF, 70 to 190°F
DEDICATED DHW UNOCCUPIED SETPOINT
(21.0 to 88.0°C)
The temperature of the dedicated DHW tank during the unoccupied periods.
Default: OFF
Requirements: This item is only available when Application Mode is set to DDHW
& the Setback / Off switch is set to Setback.
2 to 10°F
DEDICATED DHW DIFFERENTIAL
The temperature differential of the dedicated DHW tank from the DDHW SETPOINT
(1.0 to 5.5°C)
settings.
Default: 5°F (3.0°C)
Requirements: This item is only available when Application Mode is set to
DDHW.
PRIORITY OVERRIDE
OFF, AUTO, 0:20 to
The amount of time priority is given for indirect DHW before space heating
4:00 hrs
resumes.
Default: OFF
Requirements: This item is only available when Application Mode is set to RSET,
SETP or EMS, & Indirect DHW Mode is set to ON & Indirect DHW Priority is set
to ON.
35 to 100°F, OFF
WWSD OCCUPIED
The system's warm weather shutdown temperature during the occupied
(2.0 to 38.0°C)
periods.
Default: 70°F (21.0°C)
Requirements: This item is only available when the Application Mode is set to
RSET.
35 to 100°F, OFF
WWSD UNOCCUPIED
The system's warm weather shutdown temperature during the unoccupied
(2.0 to 38.0°C)
periods.
Default: 60°F (15.5°C)
Requirements: This item is only available when the Application Mode is set to
RSET & the Setback / Off switch is set to Setback.
OFF, 3 to 40 min
BOILER ALERT
Default: 20 min
Alert signal if the boiler supply temperature does not increase in temperature, after
all available boilers have been turned on, within the selected time.
Description
39 of 60