Bosch Heatronic 4000 Installation & Operating Instructions Manual page 40

4 boiler control, dhw, bacnet and modbus io heatronic 4000 2014/04 en-us
Hide thumbs Also See for Heatronic 4000:
Table of Contents
Setup Menu (6 of 6)
Item Field
Access: ADV
Access: ADV
Access: ADV
Access: ADV
Access: ADV
Access: ADV
Heatronic 4000
Range
OFF or ON
FLOW SENSOR
Default: OFF
Selects whether or not a flow sensor is used.
10 to 100 gpm
FLOW RATE 4MA
Default: 20 gpm
Sets the flow rate that corresponds to 4 mA for the flow sensor.
Requirements: This item is only available when Flow Sensor is set to ON.
100 to 2,000 gpm
FLOW RATE 20MA
Default: 500 gpm
Sets the flow rate that corresponds to 20 mA for the flow sensor.
Requirements: This item is only available when Flow Sensor is set to ON.
FLOW SENSOR PROOF
OFF, 1 to 100%
Sets the percentage of flow used for proving primary pump flow. If the flow sensor
Default: OFF
is only used for monitoring, set to OFF. This is the minimum flow required to prove
primary pump flow.
Requirements: This item is only available when Flow Sensor is set to ON.
OFF or ON
PRESSURE SENSOR
Default: OFF
Selects whether or not a pressure sensor is used.
50, 100, 150, 200, 250,
PRESSURE SENSOR RANGE
300
Selects the model of pressure sensor based on the pressure range in units of
Default: 50
PSI.
Requirements: This item is only available when Pressure Sensor is set to ON.
Description
40 of 60
BTC461503101C | 6720810369 (2018/03)