Chapter 3
Drive Port 0 Parameters
No.
Display Name
Full Name
Description
765
Psn Ref Select
Position Reference Select
Selects a position reference to the position regulator when P313 [Actv SpTqPs Mode] is
set to 10 "Psn Direct."
766
Psn Direct Stpt
Position Direct Setpoint
Provides a set point for the direct position reference and a position reference to the
position regulator when P313 [Actv SpTqPs Mode] is set to 10 "Psn Direct" and P765 [Psn
Ref Select] is set to this parameter.
767
Psn Direct Ref
Position Direct Reference
Indicates the position direct reference selected by P765 [Psn Ref Select].
136
Rockwell Automation Publication 750-PM001N-EN-P - February 2017
Values
Default:
766
Options:
1 / 159999
Default:
0
Min/Max:
–2147483648 / 2147483647
Default:
0
Min/Max:
–2147483648 / 2147483647
RW 32-bit
Integer
RW 32-bit
Integer
RO 32-bit
Integer